Taylor C708 Operator's Manual page 33

Heat treatment soft serve freezers
Hide thumbs Also See for C708:
Table of Contents

Advertisement

Use the arrow keys to program the AUTO STANDBY
TIME by increasing or decreasing the hour setting
above the cursor. Press the SEL key to advance the
cursor and program the minutes setting. Press the
SEL key to return to the previous screen with the new
time setting displayed. Press the SEL key to exit the
screen and return to the Manager's Menu.
AUTO STANDBY TIME
Agitator Operation
The AGITATOR OPERATION screen allows the manager
to select either continuous or intermittent agitator
operation.
AGITATOR OPERATION may be set to operate in the
standard mode or "with Hopper Refrig." In the standard
mode, the agitator operates during Auto, Standby, and
Heat Treat. In the "with Hopper Refrig" mode, it runs only
when the hopper is refrigerating and during the Heat,
Hold, and Soak phases of a Heat cycle, and the Cool
phase of a Heat cycle if the hopper is refrigerating. The
default is standard operation.
AGITATOR OPERATION
> Standard operation
with Hopper Refrig
Exit
Use the arrow keys to move to the desired operation and
press the SEL key to accept the selection.
Mix Level Audible
The MIX LEVEL AUDIBLE screen, when enabled, will
alert the operator with an audible tone when there is a
Mix Low or Mix Out condition. The following screen is
displayed upon selecting this option:
MIX LEVEL AUDIBLE
ENABLED
> Enable
Disable
Disable the audible tone feature by pressing the Down
Arrow key to move the arrow to Disable. Press the SEL
key to save the new setting and return to the Manager's
User Interface
00:00
Models C708 & C716
Menu. The control panel icons for Mix Low and Mix Out
will illuminate as the mix level drops in the hopper, but the
audible tone will be disabled.
Fault Description
The FAULT DESCRIPTION screen will indicate a fault
with the freezer and where the fault occurred. When no
faults are detected, the following screen will be
displayed:
FAULT DESCRIPTION
NO FAULT FOUND
Press the SEL key to display the next fault found or
return to the Manager's Menu if no other faults exist.
Pressing the SEL key anytime faults are displayed will
clear the faults, if corrected, upon returning to the menu
screen.
Listed below are the variable messages which will
appear, along with an explanation for the corrective
action.
NO FAULT FOUND—There was no fault found in the
freezer. Nothing will appear on the screen after this
variable message appears.
BEATER OVERLOAD—Place the power switch in
the OFF position. Wait 5 minutes for the machine to
cool. Press the beater reset button firmly. Place the
power switch in the ON position and restart in Auto
mode.
COMPRESSOR HPCO—Place the power switch in
the OFF position. Wait 5 minutes for the machine to
cool. Place the power switch in the ON position and
restart in Auto mode.
HOPPER THERMISTOR FAIL*—Place the power
switch in the OFF position. Call a service technician.
BARREL THERMISTOR FAIL*—Place the power
switch in the OFF position. Call a service technician.
Note: * Three codes have been set up to assist in
diagnosing bad thermistor probes. If a probe has
shorted (resistance less than 1 ohm), SHRT will
display its machine location. If the probe is open
(resistance above 1 megohm), OPEN will display. If
the actual probe environment exceeds 200°F (93°C),
the respective screen display location will read
OVER, indicating the temperature is out of range.
USER INTERFACE
5-11
5