Chapter 1
Introduction
Recycling and Disposal
For environmentally friendly recycling and disposal of this device and related accessories, contact a facility
certified to dispose of waste electrical and electronic equipment. Recycling and disposal must be done in
accordance with local regulations.
Section 1.5
Cabling Recommendations
All copper Ethernet ports on RUGGEDCOM products include transient suppression circuitry to protect against
damage from electrical transients and conform with IEC 61850-3 and IEEE 1613 Class I standards. This means that
during a transient electrical event, communications errors or interruptions may occur, but recovery is automatic.
Siemens also does not recommend using copper Ethernet ports to interface with devices in the field across
distances that could produce high levels of ground potential rise (i.e. greater than 2500 V), during line-to-ground
fault conditions.
CONTENTS
•
Section 1.5.1, "Supported Fiber Optic Cables"
Section 1.5.1
Supported Fiber Optic Cables
The following fiber optic cable types are supported under the stated conditions.
Cable Type
OM1 (62.5/125)
OM2 (50/125)
a
OM3 (50/125)
a
OM4 (50/125)
a
Laser optimized.
4
Modal Bandwidth
Wavelength (nm)
(MHz·km)
850
1300
850
1300
850
1300
850
1300
100Base-FX
200
—
500
2000
500
—
500
2000
1500
—
500
2000
3500
—
500
2000
RUGGEDCOM RS900
Installation Guide
Distance (m)
1000Base-SX
10GBase-SR
275
33
—
—
550
82
—
—
550
300
—
—
550
400
—
—
Cabling Recommendations