Parameters Of The Ai 8 X 16 Bit; Table 10-11 Parameters Of The Ai 8 X 16 Bit - Siemens SIMATIC ET 200PA SMART Operating Instructions Manual

Process
Hide thumbs Also See for SIMATIC ET 200PA SMART:
Table of Contents

Advertisement

Technical specifications
● Output voltage for transducer and cable with 22 mA
Sensor selection data
Input ranges (rated values / input resistance)
● Current
Permissible input current for current input (destruction limit)
* Cycle time = Basic conversion time per channel x Number of enabled channels
10.4.2.1

Parameters of the AI 8 x 16 Bit

Parameter assignment
The parameters are assigned using the parameter assignment dialog of HW Config
Parameters of the AI 8 x 16 Bit
The table below provides an overview of the assignable parameters and their default settings
for the AI 8 x 16 Bit.
The default settings apply when you have not assigned parameters in HW Config or you have
not changed any parameters.

Table 10-11 Parameters of the AI 8 x 16 Bit

Parameter
Diagnostic interrupt enable
Diagnostics
● Group diagnostics analog
● Wire break check
Smoothing
Measurement type
ET 200PA SMART
Operating Instructions, 06/2019, A5E34192013-AB
transducer current
(measurement resistance on module already taken into
account)
Value range
Yes / No
Yes / No
Yes / No
None
Weak
Medium
Strong
Disabled
4WMT
current
*
2WMT
current
*
≥ 18 V (when UN = 24 V)
0 to 20 mA
4 to 20 mA
± 20 mA
40 mA
Default setting
Yes
Yes
Yes
None
4WMT
current
*
ET 200PA SMART I/O modules
10.4 Analog input modules
140 Ω
140 Ω
140 Ω
Scope
Module
Channel
Channel
Channel
Module
173

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic pcs 7