Siemens SIMATIC ET 200PA SMART Operating Instructions Manual page 206

Process
Hide thumbs Also See for SIMATIC ET 200PA SMART:
Table of Contents

Advertisement

ET 200PA SMART I/O modules
10.5 Analog output modules
Technical specifications
Weight
Module-specific data
Configuration in RUN possible
Behavior of the non-assigned outputs
Supports isochronous mode
Number of outputs
Cable length
● Shielded
Voltages, currents, potentials
Rated load voltage L+
● Reverse polarity protection
● Electrical isolation
● Between channels and backplane bus
● Between channels and electronics power supply
● Between channels
● Between channels and load voltage L+
Permissible potential difference
● Between S and M
ANA
Isolation tested with
Current consumption
● From backplane bus
● From supply voltage L+
Power loss of the module
Analog value formation
Resolution, including sign
● ± 10 V; ± 20 mA; 4 mA to 20 mA; 1 V to 5 V
● 0 V to 10 V; 0 mA to 20 mA;
● Conversion time (per channel)
Transient recovery time
● With resistive load
● With capacitive load
● With inductive load
Interference suppression, error limits
● Crosstalk between outputs
Operational limit (across entire temperature range, relative to measurement range end value of the selected output range)
● Voltage output (as of product version 3)
● Current output
Basic error limit (operational limit at 25 °C, relative to the measurement range end value of the selected output range)
206
(U
)
CM
Approx. 272 g
Yes
Output the last valid output value before the parame‐
ter assignment
No
8
Max. 200 m
24 V DC
Yes
Yes
Yes
No
Yes
3 V DC
500 V DC
Max. 100 mA
Max. 340 mA
Typ. 6.0 W
11 bits + sign
12 bits max.
0.8 ms
0.2 ms
3.3 ms
0.5 ms (1 mH)
3.3 ms (10 mH)
> 40 dB
± 0.5%
± 0.6%
Operating Instructions, 06/2019, A5E34192013-AB