Siemens SIMATIC ET 200PA SMART Operating Instructions Manual page 182

Process
Hide thumbs Also See for SIMATIC ET 200PA SMART:
Table of Contents

Advertisement

ET 200PA SMART I/O modules
10.4 Analog input modules
Technical specifications
Temperature range
● Horizontal mounting position
● Vertical mounting position
Voltages, currents, potentials
Rated load voltage L+
● Reverse polarity protection
Supply voltage of the 2-wire transducer
● Short-circuit-proof
Electrical isolation
● Between the channels and backplane bus
● Between channels
● Between the channels and load voltage L+
● Between the backplane bus and load voltage L+
Isolation, designed for basic isolation
● Between the channels and backplane bus (U
● Between the backplane bus and load voltage L+
Isolation tested
● Channels from backplane bus
● Load voltage L+ from backplane bus
● Between channels
Current consumption
● From backplane bus
● From load voltage L+
Power loss of the module
Analog value formation
Measuring principle
Integration time/
interference frequency suppression (per
channel)
● Configurable
● Integration time in ms
● Basic conversion time including
182
(supply current of all connected transducers)
integration time in ms (per channel)
0 ℃ to 60 ℃
0 ℃ to 40 ℃
24 V DC/0.36 A
Yes
Yes
Short-circuit current approx. 70 mA
Yes
Permissible common-mode voltage
in the case of 4-wire transducer:
30 V DC
20 V AC
Permissible potential difference for
4-wire transducer:
30 V DC
20 V AC
Yes
75 V DC
)
ISO
60 V AC
75 V DC
60 V AC
500 V AC or 707 V DC, type test
500 V AC or 707 V DC, type test
No
Max. 100 mA
Typ. 20 mA per connected trans‐
ducer
Approx. 3.0 W
SIGMA-DELTA
60 Hz
50 Hz
Yes
Yes
19.8
23.75
23
27
Operating Instructions, 06/2019, A5E34192013-AB
10 Hz
Yes
118.8
122
ET 200PA SMART