I&M Data For Profibus Dp; Table 7-1 Structure Of Ds 248 For The Im 650 - Siemens SIMATIC ET 200PA SMART Operating Instructions Manual

Process
Hide thumbs Also See for SIMATIC ET 200PA SMART:
Table of Contents

Advertisement

Functions
7.8 Identification and maintenance data (I&M data)
7.8.1
I&M data for PROFIBUS DP
Note
Only one DP master can access the I&M data of an ET 200PA SMART at a time.
Reading and writing I&M data with SIMATIC Manager
The I&M data is displayed in the "Module status - IM 650" and "Properties - DP Slave" tabs in
SIMATIC Manager.
The M-data of modules can be entered in HW Config (e.g., in a dialog box during configuration).
The access to the I&M data takes place in accordance with IEC 61158-6.
In the H-system, the interface module from which the I&M data is to be read must be accessible
online.
Reading and writing I&M data without SIMATIC Manager
If you want to use the I&M data without using PCS 7 or SIMATIC Manager, you must access the
data in accordance with the specifications of the PROFIBUS Guideline – Order No. 3.502,
Version 1.1 May 2003.
In the AS 410H, you must address the interface module (slot 245 or 246) from which the I&M
data is to be read. Slot 245 designates the left interface module and slot 246 the right interface
module on the BM IM/IM.
Example of reading the I&M data
You can selectively access specific I&M data using Read data record. A two-level access is
necessary for this:
1. Data record 248 has a directory containing the associated data record numbers
Table 7-1
Contents
Header information
ID of the contents list
Index of the contents list
Length of the following blocks in bytes
Number of blocks
Block information for the I&M data
SSL ID
Associated data record number
Length of the data record
Index
84
for the various indices (refer to the following table).
Structure of DS 248 for the IM 650
Length (bytes)
2
2
2
2
2
2
2
2
Operating Instructions, 06/2019, A5E34192013-AB
Coding (hex)
00 01
00 00
00 08
00 05
F1 11
00 E7
00 40
00 01
ET 200PA SMART