Table 8-7 Error Type Of The Channel-Related Diagnostics - Manufacturer-Specific - Siemens SIMATIC ET 200PA SMART Operating Instructions Manual

Process
Hide thumbs Also See for SIMATIC ET 200PA SMART:
Table of Contents

Advertisement

Interrupt, error and system messages
8.3 S7 diagnostics
Table 8-7
Error type of the channel-related diagnostics - manufacturer-specific
Error type
Error text
10000
16
Parameter as‐
B
D
signment error
10001
17
No sensor or
B
D
load voltage
10010
18
Fuse defective
B
D
10011
19
Communication
B
D
error
10100
20
Ground error
B
D
10101
21
Reference
B
D
channel fault
10110
22
Hardware inter‐
B
D
rupt lost
10111
23
Warning
B
D
11000
24
Tripping
B
D
11001
25
Safety-oriented
B
D
tripping
11010
26
External error
B
D
102
Meaning
Parameter assignment error, e.g.:
● Module cannot use the parameter (unknown, invalid
combination, etc.)
● Module parameters not assigned
● User calibration does not correspond to the parameter
assignment
● Calibration error
The following voltages can be missing:
● External supply voltage
● Voltage for operation of the module
The user-replaceable fuse has blown
General communication error
For HART modules: Communication error with the HART field
device
Ground error (common mode error) e.g.:
● The permissible common mode voltage has been
exceeded in the case of non-isolated channels
● The M line is broken in the case of isolated channels
Error on the reference channel
At least one hardware interrupt could not be signaled
For HART modules: Additional status information of the
HART field device is available
There could be a warning, if limit values like:
● Speed
● Load current
are exceeded
For HART modules: Maintenance request of the HART field
device
Tripping can be, for example:
● Circuit breaker has tripped due to short-circuit,
asymmetry, ground fault
● Thermistor has tripped
Trigger/cause for safety-related tripping is pending
External (process-side) error, e.g.:
● Sensor error
● Actuator error
● Sensor data is incorrect
For HART modules: Malfunction of the HART field device
Remedy
Correction of the pa‐
rameter assignment
Correction of the proc‐
ess wiring
Replace the fuse
Check the HART field
device, check the wir‐
ing
Correction of the proc‐
ess wiring
Replace the reference
channel module
Correction tuning of
program/
process/module
Correction tuning of
program/
process/module
Eliminate the cause of
tripping and acknowl‐
edge, if necessary
Eliminate the cause of
tripping
Replace sensor/
actuator/ correct proc‐
ess wiring