Short-circuit of the sensor supply Vs
The status LED of the sensor supply goes out in the event of a short-circuit of the sensor supply
Vs, irrespective of the parameter assignment.
Wire break
In order for a wire break to be detected even in case of "0" signal, a resistance of 10 to 18
kilohms must be wired parallel to the sensor contacts.
10.3
Digital output modules
Overview of properties
The table below presents the ET 200PA SMART digital output modules based on their most
important properties.
Table 10-5
Properties
Number of outputs
Output current
Rated load voltage
Suitable for
Configurable
diagnostics
Diagnostic interrupt
Substitute value output
10.3.1
Digital output module DO 32 x DC 24 V/ 0.5 A
Article numbers
Standard module: 6ES7 650-8EK80-0AA0
Module with conformal coating: 6ES7 650-8EK80-1AA0
ET 200PA SMART
Operating Instructions, 06/2019, A5E34192013-AB
Digital output modules
Module
DO16 x 24V/0.5A
6ES7650-8EK70-xAA0
16
Isolated in groups of 16
0.5 A
24 V DC
Solenoid valves, DC contactors and signal lamps
Yes
Yes
Yes (channel-specific)
ET 200PA SMART I/O modules
10.3 Digital output modules
DO32 x 24V/0.5A
6ES7650-8EK80-xAA0
32
Isolated in groups of 8
0.5 A
24 V DC
No
No
No