ET 200PA SMART I/O modules
10.5 Analog output modules
Properties
● 8 outputs in one group
● The output can be configured for each channel:
● Resolution 12 bits
● HART-compliant (for current output)
● Configurable diagnostics
● Configurable diagnostic interrupt
● Floating relative to backplane bus interface and load voltage
● Configuration in Run (CiR) supported
Note
When the rated load voltage (L+) is switched off and on, the outputs can output incorrect
voltage/current values for approximately 500 ms.
202
Possible selection
Current output
Voltage output
As of product version
Product version 1
Product version 3
Operating Instructions, 06/2019, A5E34192013-AB
Ranges
● 0 mA to 20 mA
● 4 mA to 20 mA
● +/-20 mA
● 1 V to 5 V
● 0 V to 10 V
● +/-10 V