Table 10-10 Overview Of The Parameters Of Sm 331; Ai 8 X 13 Bit - Siemens SIMATIC ET 200PA SMART Operating Instructions Manual

Process
Hide thumbs Also See for SIMATIC ET 200PA SMART:
Table of Contents

Advertisement

ET 200PA SMART I/O modules
10.4 Analog input modules
Parameter

Table 10-10 Overview of the parameters of SM 331; AI 8 x 13 Bit

Parameters
Measurement
● Measurement type
● Measuring range
● Temperature coefficient
● Interference frequency
suppression
● Temperature unit
* only Pt 100 Standard, Ni 100 Standard, Ni 1000 Standard, LG-Ni 1000 Standard
162
Range of values
disabled
Voltage V
Current I
Resistance R, PTC
Thermal resistance RTD,
silicon temperature sensors
Voltage
± 50 mV; ± 500 mV; ±1 V;
1 V to 5 V
± 5 V; 0 V to 10 V; ± 10 V
Current
0 mA to 20 mA; 4 mA to 20 mA; ± 20 mA
Resistance
0 Ω to 600 Ω; 0 kΩ to 6 kΩ; PTC
Thermoelectric resistance (linear)
Pt 100 Klima / Standard
Ni 100 Klima / Standard
Ni 1000 Klima / Standard
LG-Ni 1000 Klima / Standard
KTY83/110
KTY84/130
Pt 100
0.003850 Ω/Ω/ °C (IST-90)
Ni 100 / Ni 1000
0.006180 Ω/Ω/ °C
LG-Ni 1000
0.005000 Ω/Ω/ °C
50 Hz; 60 Hz
Degrees Centigrade, degrees Fahren‐
heit, Kelvin*
Default
Parameter
type
V
± 10 V
± 20 mA
600 Ω
dynamic
Pt 100
Standard
0.003850
50 Hz
degrees
Centigrade
Operating Instructions, 06/2019, A5E34192013-AB
Scope
Channel
Module
ET 200PA SMART

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic pcs 7

Table of Contents