7.4 Time stamping of the input signals with IM 650
7.4.4

Time synchronization for time stamping

Requirements
The following requirements apply to the time synchronization for time stamping:
● There must be a time-of-day master, e.g. SICLOCK TM, available in the automation system
that operates with a synchronization interval of 10 s.
● The time-of-day frame must be passed via the PROFIBUS DP interface of the CPU.
● A synchronization interval of 10 s must be assigned for the IM 650.
Time synchronization for high-precision time stamping with 1 ms accuracy
You must realize the time synchronization for the high-precision time stamping with the
following hardware components and settings:
● Time-of-day master: SICLOCK TC 400 with GPS synchronization
Parameters to be set for SICLOCK TM:
Synchronization /
Redundancy
Inputs
Ethernet
● Ethernet: CP 443‑1; 6GK7443‑1EX30‑0XE0
Parameters to be set for Ethernet CP:
Parameter
Forward time
Switch on the time synchronization in SIMATIC procedure
● CPU 410:
Parameters to be set for the CPU:
78
Path / tab
Synchronization
Input general
Input E1
LAN general
LAN 1-5
Adr1 is given as an example. Other LAN‑connections / addresses have other
parameter numbers accordingly.
LAN extra
Parameter
(with number from the SI‐
CLOCK parameter menu)
Mode (218)
Step pos. (219)
Step neg. (220)
Input type (230)
E1 active / passive
DCF alarm (239)
LAN timeout (349)
Adr1 protocol (e.g. 350)
Adr1 send (e.g. 351)
Adr1 def. (e.g. 352)
SNTP server (550)
Value
from LAN to station
Operating Instructions, 06/2019, A5E34192013-AB
Value
Ramp
Micro step
DCF
TTY passive
5
0.5 s
Layer 2 - S5
10 s
broadcast
Off