Commissioning; Profibus Dp; Commissioning The Dp Slave; Table 5-1 Software Requirements For Commissioning - Siemens SIMATIC ET 200PA SMART Operating Instructions Manual

Process
Hide thumbs Also See for SIMATIC ET 200PA SMART:
Table of Contents

Advertisement

Commissioning

5.1

PROFIBUS DP

5.1.1

Commissioning the DP slave

Software requirements
Table 5-1
Software requirements for commissioning
Configuration software
used
PCS 7
Requirements for commissioning
The following requirements must be met in order to commission the ET 200PA SMART:
● DP slave installed
● PROFIBUS address set on the DP slave
● Bus connector connected
● If the DP slave is located on the end of the segment, then the terminating resistor is
connected to the DP slave.
● DP slave configured
● Supply voltage for DP master switched on
● Configuration downloaded to the DP master
● DP master switched to RUN operating state
Commissioning the DP slave
Commission the DP slave as follows:
1. Switch on the supply voltage for ET 200PA SMART.
2. If necessary, switch on the supply voltage for the load.
ET 200PA SMART
Operating Instructions, 06/2019, A5E34192013-AB
Version
Explanations
As of V 8.1
Configure the IM 650 from the hardware catalog of HW Config
PCS7_V8.1 (ET 200PA SMART)
5
, Profile
53