Transferring the parameters from the MMC memory card into the inverter (download)
Table 4- 16
Parameters
P0003 = 3
P0010 = 30
P0803 = 2
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA
4.7 Data backup with the operator panel and memory card
Transferring data from the memory card to the inverter
Description
3: Expert
30: Initiating parameter transfer
2: Transfer data to the EEPROM (of the inverter) from the MMC. "RDY" LED flashes.
If the upload procedure is successful, P0010 and P0803 are set to 0 and the "RDY"
LED lights up.
If the download procedure is unsuccessful, F0061 or F0062 is displayed and the
LED "SF" (red) lights up. In this case, make another attempt to transfer data.