Transferring the parameters from the MMC memory card into the inverter (download)
Table 4- 16
Parameters
P0003 = 3
P0010 = 30
P0803 = 2
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA
4.7 Data backup with the operator panel and memory card
Transferring data from the memory card to the inverter
Description
3: Expert
30: Initiating parameter transfer
2: Transfer data to the EEPROM (of the inverter) from the MMC. "RDY" LED flashes.
If the upload procedure is successful, P0010 and P0803 are set to 0 and the "RDY"
•
LED lights up.
If the download procedure is unsuccessful, F0061 or F0062 is displayed and the
•
LED "SF" (red) lights up. In this case, make another attempt to transfer data.
Commissioning