BICO technology: example

Example: Shifting a basic PLC functionality into the inverter
A conveyor system is to be configured in such a way that it can only start when two signals
are present simultaneously. These could be the following signals, for example:
● The oil pump is running (the required pressure level is not reached, however, until after
● The protective door is closed
The task is realized by inserting free blocks between the digital input 0 and the internal ON
command for the motor and interconnecting them.
DI 0
DI 1
Figure 1-3
Table 1- 13
Parameter
P0003 = 3
P0700 = 2
P0701 (e.g.) = 99
P0702 (e.g.) = 99
P2800 = 1
P2801 [In000] = 1
P2802 [In000] = 1
P2850 = 5.0
P2849 = r0722.0
P2810 [In000] = r2852
P2810 [In001] = r0722.1
P0840 = r2811
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA
1.5 Extended adaptation options (parameterization for advanced level personnel)
five seconds)
P2850 = 5,0 [s]
T
P2849
r0722.0
Index [0]
Timer
r0722.1
Example: Signal interconnection for interlock
Parameterizing an interlock
Description
Enable expert access to parameters
Select the command source: Digital inputs
Enable/"open" digital input 0 (DI0) for BICO parameterization
Enable/"open" digital input 1 (DI1) for BICO parameterization
Group enable all freely-programmable function blocks (FFB)
Individual enable of the AND function block
Individual enable of the TIMER function block
Set the TIMER delay time: 5 seconds
Connect the status of DI0 to the TIMER input
r0722.0 = Parameter that displays the status of digital input 0.
Connect the TIMER output to the 1st input of the AND
Connect the status of DI1 to the 2nd AND input
r0722.1 = Parameter that displays the status of digital input 1.
Connect the AND output to the control command ON/OFF1
P2800
0
r2852
P2810
Index [0]
Index [1]
P2801[0]
P0840
&
r2811
Index [0]