Functions
5.10 Technological functions
Input values
Table 5- 57
Parameter Description
P1200 =
...
Table 5- 58
P1200
0
1
2
3
4
5
6
Table 5- 59
Parameter Description
P1202 =
...
P1203 =
...
140
Main function parameters
Flying restart
0: locked (factory setting),
1 - 6 Active
Overview: the "flying restart" function
Flying restart active
Flying restart locked (factory setting)
Flying restart always active
Flying restart active after:
Power ON
•
Faults
•
OFF2
•
Flying restart active after
Faults
•
OFF2
•
Flying restart always active
Flying restart is active after
Power ON
•
Faults
•
OFF2
•
Flying restart is active after
Faults
•
OFF2
•
Additional commissioning parameters
Motor current: Flying restart
(entered in %): 10 % ... 200 %, factory setting 100 %
Defines the search current with respect to the rated motor current (P0305) that is
present when the "flying restart" function is used.
Search rate/speed: Flying restart
(entered in %): 10 % ... 200 %, factory setting 100 %
Sets the factor by which the output frequency changes during the flying restart to
synchronize itself with the running motor.
Search direction
-
Search performed in both directions, startup in
direction of setpoint
Search performed in both directions, startup in
direction of setpoint
Search performed in both directions, startup in
direction of setpoint
Search performed in direction of setpoint only
Search performed in direction of setpoint only
Search performed in direction of setpoint only
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA