1.4 Frequently required parameters

1.4
Frequently required parameters
Parameters that in many cases help
Table 1- 1
This is how you filter the parameter list to keep the number of displayed parameters transparent
Parameter

Description

P0003 =
User access level
1: Standard: Allows access to the most frequently used parameters (factory setting)
2: Extended: Extended access, e.g. to inverter I/O functions
3: Expert: To be used by experts
P0004 =
Parameter filter
0: All the parameters are displayed (factory setting).
2: Inverter
3: Motor - data of the motor and output filter are displayed
4: Speed encoder - parameters for the optional speed encoder are displayed
Table 1- 2
How to switch to commissioning mode or restore the factory setting
Parameter
Description
P0010 =
Commissioning parameters
0: Ready (factory setting)
1: Perform quick commissioning
30: Factory setting - initiate restore factory settings
Table 1- 3
How to determine the firmware version of the Control Unit
Parameter
Description
r0018
The firmware version is displayed:
Table 1- 4
This is how you reset the parameters to the factory setting
Parameter
Description
P0010 = 30
30: Factory setting - initiate restore factory settings
P0970 = 1
1: Resetting - restoring all parameters to the factory setting
(Exception: Password-protected parameters of the safety functions are not reset!)
Table 1- 5
This is how you select the command source of the control signals (ON/OFF, reversing) of the inverter
Parameter
Description
P0700 =
0: Factory default setting
1: Operator Panel
2: Digital inputs (P0701 ... P0709); factory setting non-fieldbus-capable inverters
4: USS on RS 232
5: USS on RS 485 (not available for CU240S DP or CU240S DP-F)
6: Fieldbus (P2050 ... P02091); (factory setting for fieldbus-capable inverters)
14
CU240S and CU240E Control Units, FW 3.2
Operating Instructions, 03/2009, A5E02440075B AA