Electrical connections
5.3.4

ATEX - Zone 1 (20)

Transmitter design: II 2 G (1D) Ex [iaD] ib IIC T6
Zone 0, Zone 1,
Fig. 18
A Sensor
B Transmitter in housing with IP 20 ingress
protection
For instruments in Zone 1, the transmitter must be installed in a suitable housing with IP 20
ingress protection. The input for the supply isolator must have an [Ex ib] design.
The user must ensure that the sensor instrumentation meets the requirements of applicable
explosion protection standards. It can be installed in Zone 0, Zone 1, or Zone 20.
5.3.5

ATEX - Zone 2

Transmitter design: II 3 G Ex nA II T6
Fig. 19
A Sensor
B Transmitter in housing with IP 54 ingress
protection
For instruments in Zone 2, the transmitter must be installed in a suitable housing with ingress
protection of at least IP 54.
In the event of a disturbance, it must be ensured that the supply voltage cannot exceed the
normal voltage by more than 40 %.
28
Zone 20
J
A
Ex Zone 2
J
A
Ex Zone 1
D
i
a
ia
B
C Supply isolator [Ex ib]
D Interface for LC display
D
B
C Supply isolator
D Interface for LC display
TTH300
Safe area
ib
ib
C
A00147
Safe area
C
A00148
OI/TTH300-EN