ABB TTH300 Operating Instruction page 58

Head mounted temperature transmitter
Hide thumbs Also See for TTH300:
Table of Contents

Advertisement

Configuration via the LC display with control buttons
Area
Device status message
(on the display)
Electronics
Configuration error
Sensor
Sensor 1 + 2 redundancy failure
Sensor
Sensor 1 redundancy: Short circuit
Sensor
Sensor 1 redundancy: Wire break
Sensor
Sensor 2 redundancy, short circuit
Sensor
Sensor 2 redundancy, wire break
Important
If the remedial measures listed for the diagnostic information do not improve the status of the
device, please consult ABB Service.
58
Cause
Error
Error
Maintenance required
Maintenance required
Maintenance required
Maintenance required
TTH300
Remedy
Validate configuration
Check sensor / sensor
connection
Rectify short circuit at sensor
1 or replace sensor 1
Rectify break at sensor 1 or
replace sensor 1
Rectify short circuit at sensor
2 or replace sensor 2
Rectify break at sensor 2 or
replace sensor 2
OI/TTH300-EN