Configuration via the LC display with control buttons
8.2.6

Diagnostic information on the LC display

If diagnostic information is available, a message consisting of a symbol or letter (device status)
and a number (DIAG NO.) will appear at the bottom of the process display.
The diagnostic messages are divided into the following groups in accordance with the NAMUR
classification scheme:
The error can then be read in plain-text format on the "Diagnostics" information level.
Additionally, the diagnostic messages are divided into the following areas:
Operating conditions Diagnostics for ambient and process conditions
44
Symbol -
Description
Letter
I
OK or Information
C
Check Function
S
Off Specification
M
Maintenance Required Request service to prevent the measuring point
F
Failure
Area
Description
Electronics
Diagnostics for device hardware
Sensor
Diagnostics for sensor elements and supply lines
Installation /
Diagnostics for communication interface and parameterization /
Configuration
configuration
Device is functioning or information is available
Device is undergoing maintenance
(e.g., simulation)
Device or measuring point is being operated
outside of the specifications
from failing
Error; measuring point has failed