Zone 1 (20); Zone 2 - ABB TTH200 Commissioning Instruction

Head mounted temperature transmitter
Hide thumbs Also See for TTH200:
Table of Contents

Advertisement

Electrical connection
4.6.4

Zone 1 (20)

Transmitter design: II 2 G (1D) Ex [iaD] ib IIC T6
Zone 0, Zone 1,
Fig. 13
A Sensor
B Transmitter in housing with IP 20 degree
of protection
For instruments in Zone 1, the transmitter must be installed in a suitable housing with IP 20
degree of protection. The input for the supply isolator must have an [Ex ib] design.
The user must ensure that sensor instrumentation meets the requirements of applicable Ex
standards. It can be installed in Zone 0, Zone 1, or Zone 20.
4.6.5

Zone 2

Transmitter design: II 3 G Ex nA II T6
Fig. 14
A Sensor
B Transmitter in housing with IP 54 degree
of protection
For instruments in Zone 2, the transmitter must be installed in a suitable housing with a degree
of protection of at least IP 54.
In the event of a disturbance, it must be ensured that the supply voltage cannot exceed the
normal voltage by more than 40 %.