Meter Design For Nepsi Intrinsic Safety, Atex/Iecex Intrinsic Safety; (Zone 0 /20), And Cfmus Division 1, Zone 0/20 - ABB LST300 Operating Instruction

Compact ultrasonic level transmitter
Hide thumbs Also See for LST300:
Table of Contents

Advertisement

54
Entity parameters for L2 display
Temperature
Temperature
class – Gas
class – Dust
T4
T135 °C
T4
T135 °C
T5
T100 °C
T6
T85 °C
Entity parameters for L7 display
Temperature
Temperature
class – Gas
class – Dust
T4
T135 °C
T4
T135 °C
T5
T100 °C
T6
T85 °C
Entity parameters for L0 display
Temperature
Temperature
class – Gas
class – Dust
T4
T135 °C
T4
T135 °C
T5
T100 °C
T6
T85 °C
The devices must be installed in a protected environment in
accordance with the specific conditions on the test certificate .
Pollution degree 3 (refer to IEC 60664-1) must not be exceeded
for the macro environment of the device . The device conforms
to degree of protection IP66 / IP67 . If the device is installed as
intended, this requirement is met by the housing as standard .
When connected to the line supply, the electrical circuits must
not exceed overvoltage category III . When not connected to the
line supply, the electrical circuits must not exceed overvoltage
category II .
Meter design for NEPSI intrinsic safety,
ATEX/IECEx intrinsic safety (Zone 0 /20),
and cFMus division 1, Zone 0/20
Meter design for NEPSI intrinsic safety, Ex protection code is
C6 .
Meter design for ATEX/IECEx intrinsic safety (Zone 0/20), Ex
protection code is E6 .
Meter design for cFMus division 1, Zone 0/20, Ex protection code
is F4 .
IMPORTANT (NOTE)
For applications in US and Canada, when the temperature
under rated conditions is higher than 60 °C at the entry point or
60 °C at the branching point of conductors, accessories such as
cable, gland or conductors in conduit with minimum
temperature specification of 60 °C must be selected .
L S T 3 0 0 | C O M PA C T U LT R A S O N I C L E V E L T R A N S M I T T E R | L S T 3 0 0 – E N R E V. E
IMPORTANT (NOTE)
The devices may only be operated in explosive areas if the
Ambient temperature
limitation
housing covers have been fully closed .
-40 to 60 °C
-40 to 60 °C
-40 to 56 °C
Static hazard clean only with a damp cloth .
-40 to 44 °C
Avertissement – Danger statique Nettoyez uniquement avec
un chiffon humide .
Ambient temperature
limitation
IMPORTANT (NOTE)
-40 to 85 °C
"C6" digit means that customers choose NEPSI Intrinsically
-40 to 70 °C
Safe method of protection on the product .
-40 to 40 °C
Dedicated check box is to be marked by the manufacturer .
-40 to 40 °C
IMPORTANT (NOTE)
"E6" digit means that customers choose ATEX or IECEx
Intrinsically Safe method of protection on the product .
Ambient temperature
limitation
Dedicated check box is to be marked by the manufacturer .
-40 to 85 °C
IMPORTANT (NOTE)
-40 to 70 °C
"F4" digit means that customers choose FM US or FM C
-40 to 56 °C
Intrinsically Safe method of protection on the product .
-40 to 44 °C
Dedicated check box is to be marked by the manufacturer .
NEPSI approval design for China
Ex ia IIC T6 . . . T 4 Ga Ex iaD 20 T85° C
For electrical parameters, refer to cert, GYJXXXXXXX
EC type-examination certificate FM15ATEX0063X
Designation:
II 1 G Ex ia IIC T6 . . . T 4 Ga - II 1 D Ex ia IIIC T85° C
For electrical parameters, refer to cert, FM15ATEX0063X
Certificate of conformity IECEx FME 15 . 0010X
Designation:
Ex ia IIC T6 . . . T 4 Ga - Ex ia IIIC T85° C
For electrical parameters, refer to cert, IECEx FME 15 .0010X
FM approval design for the USA and Canada
IS/Sec . Intrinseque (Entity) CL I
ZONE 0 AEx/Ex ia IIC T6 . . . T 4
CL I/DIV 1/GP ABCD IS - CL II,III DIV 1/GP EFG
IS Control Drawing number: 3KXL065035U0009
Supply power terminals
Refer to the tables below
Operation temperature ranges
• Ambient operating temperature between -40 °C and 85 °C
(-40 °F and 185 °F)
• Dependance on the temperature class as detailed in the
tables below
WARNING