Description Of Diagnostic Information - ABB TTH300 Operating Instruction

Head mounted temperature transmitter
Hide thumbs Also See for TTH300:
Table of Contents

Advertisement

8.3.5

Description of diagnostic information

Area
Device status message
(on the display)
Sensor
Sensor drift
Sensor
S1 line resistance too high
Sensor
S1 short circuit
Sensor
S1 wire break
Sensor
S2 line resistance too high
Sensor
S2 short circuit
Sensor
S2 wire break
Operating
S1 measurement range overflow
conditions
Operating
S1 measurement range underflow
conditions
Operating
S2 measurement range overflow
conditions
Operating
S2 measurement range underflow
conditions
Operating
Device temperature out of spec.
conditions
Electronics
Device error
Electronics
Device not calibrated
Electronics
Device being simulated
OI/TTH300-EN
Configuration via the LC display with control buttons
Cause
Out of specification
Maintenance required
Error
Error
Maintenance required
Error
Error
Out of specification
Out of specification
Out of specification
Out of specification
Out of specification
Error
Out of specification
Functional check
TTH300
Remedy
Sensor adjustment
Sensor 1: Remove corrosion
at the connections or reduce
line length
Sensor 1: Rectify short circuit
or replace sensor 1
Sensor 1: Rectify wire break
or replace sensor 1
Sensor 2: Remove corrosion
at the connections or reduce
line length
Sensor 2: Rectify short circuit
or replace sensor 2
Sensor 2: Rectify wire break
or replace sensor 2
Adapt S1 measurement range
to suit measuring task
Adapt S1 measurement range
to suit measuring task
Adapt S2 measurement range
to suit measuring task
Adapt S2 measurement range
to suit measuring task
Check environment; reposition
measuring point if required
Replace device
Calibrate device
Terminate simulation