Important
If the remedial measures listed for the diagnostic information do not improve the status of the
device, please consult ABB Service.
46
Display,
Display,
Cause
device
DIAG.
status
NO.
F
51
Short circuit, sensor 2
F
52
Wire break, sensor 2
F
53
Above sensor range, sensor 2
F
54
Below sensor range, sensor 2
F
65
Configuration defective
M
66
No sensor detected at sensor 1
in redundancy configuration
M
67
No sensor detected at sensor 2
in redundancy configuration
M
68
Sensors exceeded specified drift
window
C
71
Reconfiguration is running
F
72
Incorrect application
I
74
Calibration of analog output
active
C
75
Analog output in simulation
S
76
Above range
S
77
Limit HIGH HIGH
S
78
Limit LOW LOW
S
79
Limit HIGH
S
80
Limit LOW
TTH300
Remedy
Check sensor connection
Check sensor connection
Check measuring limits
Check measuring limits
Check configuration:
A) Wrong device
B) Span is too small
C) Incorrect configuration data
Check connection
Check connection
Calibrate sensors
Terminate reconfiguration
Check configuration,
connections; reset to factory
settings
Terminate compensation
Terminate simulation
Check parameters:
A) Sensor limits exceeded
B) Span is too small
Upper limit value: Alarm
Lower limit value: Alarm
Upper limit value: Warning
Lower limit value: Warning