ABB TTH300 Operating Instruction page 42

Head mounted temperature transmitter
Hide thumbs Also See for TTH300:
Table of Contents

Advertisement

Configuration via the LC display with control buttons
8.2.3.4
Menu: Process Alarm
Menu / Parameter
... / Process Alarm
Failure-signal
8.2.3.5
Menu: Communication
Menu / Parameter
... / Communication
HART Tag
Address (multidrop)
HART Burstmode
HART Resp. Preambles
8.2.3.6
Menu: Calibrate
Menu / Parameter
... / Calibrate
Measured range
Analog output
... / ... / Measured range
Apply Lower Range
Apply Upper Range
... / ... / Analog Output
Trim 4 mA
Trim 20 mA
42
Value range
Upscale
Downscale
Value range
8 characters
0 ... 15
Status (on / off)
Command # (1, 2, 3, 33)
5 ... 20
Value range
3,500 ... 4,500 mA
19,500 ... 20,500 mA
Description
In the event of an error, the current (e.g., 3.6 mA) is
output.
In the event of an error, the current (e.g., 22 mA) is
output.
Description
Indicates measuring points
Address range in multidrop mode
(0 means that multidrop mode is not active)
Switches burst mode on or off
Sets the HART command to be sent cyclically
Number of preambles to be used for sending
Description
Selects submenu "Measured range"
Selects submenu "Analog Output"
The current reading (PV) is used as the lower range
limit (4 mA).
The current reading (PV) is used as the upper range
limit (20 mA).
Adjusts the current output with a 4 mA setpoint
Adjusts the current output with a 20 mA setpoint
TTH300
OI/TTH300-EN