Beretta EXCLUSIVE C Installer And User Manual page 21

Hide thumbs Also See for EXCLUSIVE C:
Table of Contents

Advertisement

Available languages

Available languages

FRI
FRI
18/05/2013
MENU
MENU
INFO
INFO
HOT WATER TEMPERATURE
HOT WATER TEMPERATURE
HOT WATER ONLY
HEATING AND HOT WATER
- Through the REC10 it is possible to access, using the TECHNICAL
menu, a series of parameters that can be programmed to allow you to
personalise the operation of the boiler based on the type of system.
- Then set the parameters according to the desired operating modes.
5.2.1
Boiler configuration
- Access the technical parameters as explained in the section "4.1 Access
to the technical parameters" .
- Select PARAMETERS with the "up" and "down" keys, confirming the
selection.
INSTALLATION
INSTALLATION
PARAMETERS
PARAMETERS
TERMOREGOLAZIONE
THERMOREGULATION
WEATHER COMPENSATION
RANGE RATED
RANGE RATED
CALIBRATION
CALIBRATION
INSTALLER
INSTALLER
Select from among the following options with the "up" and "down",
-
keys, confirming the selection.
PLANT
PLANT
12:17
1.3 bar
STATE
STATE
42
°C
SET
SET
STATE
STATE
BOILER
BOILER
MAIN ZONE
MAIN ZONE
BOILER
BOILER
OFF
OFF
SUMMER
WINTER
TECHNICAL
TECHNICAL
ANTI-CYCLE FUNCTION
TIMER OFF CH
RESET TIMERS CH
RESET CH TIMERS
DHW THERMOSTAT
DHW THERMOSTAT
PREHEATING
INSTALLER
INSTALLER
-
TIMER OFF CH
This parameter allows you to change the TIMER OFF CH, regarding
the delay time introduced for re-igniting the burner in the face of an off
due to the heating temperature being reached. The factory setting for
this parameter is 3 minutes and can be set to a value between 0 min
and 20 min selecting the desired one with the "up" and "down", keys
confirming the selection.
ANTI-CYCLE FUNCTION
TIMER OFF CH
-
RESET TIMERS CH
This parameter allows you to reset the REDUCED HEATING MAXIMUM
OUTPUT TIMING, during which the speed of the fan is limited to 75%
of the maximum heating output that has been set, and the TIMER OFF
CH. The factory setting for this parameter is FUNCTION NON ACTIVE,
select FUNCTION ACTIVE using the keys "up" and "down", confirming
the selection for resetting the timings.
RESET CH TIMERS
RESET TIMERS CH
FUNCTION NOT ACTIVE
FUNCTION NOT ACTIVE
FUNCTION ACTIVE
FUNCTION ACTIVE
INSTALLER
INSTALLER
- DOMESTIC HOT WATER THERMOSTAT
This parameter allows you to set the type of DOMESTIC HOT WATER
THERMOSTAT.
The factory setting for this parameter is RELATED, i.e. for domestic hot
water the boiler switches off at setpoint +5°C and restarts at setpoint
+4°C.
To select the ABSOLUTE values, where the boiler for domestic hot water
will still switch off at 65°C and restart at 63°C, use the keys "up" and
"down".
DHW THERMOSTAT
DHW THERMOSTAT
INSTALLER
INSTALLER
PARAMETERS
PARAMETERS
PREHEATING
3
MIN
RELATED
RELATED
ABSOLUTE
ABSOLUTE
ENGLISH
21