Flash Adaptation Without Outdoor Sensor (Room Temperature Dependent) - Samson TROVIS 5579 Mounting And Operating Instructions

Automation system trovis 5500. heating and district heating controller
Table of Contents

Advertisement

Functions of the heating circuit
Functions
Room sensors RF1/2/3
Flash adaptation
Parameters
Day set point
Night set point
5.8.1 Flash adaptation without outdoor sensor (room temperature
dependent)
The flow temperature control starts with Flow day set point in rated operation or with Flow
night set point in reduced operation as no set points calculated using characteristics exist
without an outdoor sensor. The Cycle time determines the intervals at which the flow temper-
ature set point is corrected by 1 °C. The heating is then always switched off as soon as the
room temperature exceeds the Day set point or Night set point by 2 °C. Heating first starts
again when the room has cooled off and the room temperature is 1 °C above the Set point .
A Gain K
set to a value other than 0 causes a direct increase/decrease in flow temperature
P
set point when a sudden deviation in room temperature arises. A Gain K
recommended.
Functions
Room sensors RF1/2/3
Outdoor sensor AF1/2
Flash adaptation
Parameters
Day set point
Night set point
Parameters
Flow day set point
Flow night set point
80
EB 5579 EN
WE
Configuration
0
CO1, 2, 3 -> F01 - 1
0
CO1, 2, 3 -> F09 - 1
20 min
Cycle time / 1 to 100 min
0
K
(gain) / 0 to 25
P
WE
Rotary switch / Range of values
20 °C
Top, middle, bottom / 0 to 40 °C
15 °C
Top, middle, bottom / 0 to 40 °C
WE
Configuration
0
CO1, 2, 3 -> F01 - 1
1
CO1 (2, 3) -> F02 - 0
0
CO1, 2, 3 -> F09 - 1
20 min
Cycle time / 1 to 100 min
0
K
(gain) / 0 to 25
P
WE
Rotary switch / Range of values
20 °C
Top, middle, bottom / 0 to 40 °C
15 °C
Top, middle, bottom / 0 to 40 °C
WE
Parameter level / Range of values
50 °C
PA1, 2, 3 / 5 to 130 °C
30 °C
PA1, 2, 3 / 5 to 130 °C
setting of 10.0 is
P