10.1.1.1 Diagnostic Description For Vbg-Pb-K20-D-Bv - Pepperl+Fuchs AS-I 3.0 PROFIBUS Manual

In stainless steel
Table of Contents

Advertisement

AS-i 3.0 PROFIBUS Gateway in Stainless Steel
PROFIBUS DP
The conditions when to set the ExtDiag bit can be chosen using the user parame-
ters or the commands of the command interface.
The GSD file includes the following presettings:
The diagnosis transmitts ec-flags, delta list and LPF.
ExtDiag will be set if ConfigError = 1 and APF = 1. ExtDiag will not be set if
there is a periphery fault.
If a double master is being used, the data for AS-i circuit are transmitted in the
user parameter bytes 4 to 6. For circuit 2 3 additional bytes are added.

10.1.1.1 Diagnostic description for VBG-PB-K20-D-BV

DP diagnostics - single master
PDU byte
1
2
3
4
5
6
7
8
9
10
11
12
13
14
...
20
21
...
28
42
user byte
station_status 1
station_status 2
station_status 3
master address
ident high
ident low
1
header
2
type
3
slot
4
spec
5
ec-flags (high)
6
ec-flags (low)
7
delta (0...7)
8
delta (8...15)
...
...
14
delta (56...63)
15
LPF (0...7)
...
...
22
LPF (56 ... 63)
DP
DP/V1
user
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
...
4
4
...
4
Tab. 10-2.