Ups With Bypass Module Startup - Avaya 1 Series Site Preparation, Installation And Operator's Manual

200-240 v
Table of Contents

Advertisement

Installation

UPS with Bypass Module Startup

To start up the UPS:
40
1. Verify the Bypass switch on the Bypass Module rear panel is in
the NORMAL position (see Figure 5 on page 32 or Figure 6 on
page 33).
2. Steps 3 through 8 are for changing the output voltage. The
output voltage is factory-configured for 208V. If you do not
need to change the output voltage, skip to Step 10.
Use the following table to select the correct output voltage
according to your Bypass Module.
Bypass Module Model Number
60-Hz BDM 208: 120/208
60-Hz BDM 208/240: 120/240
60-Hz BDM 208/240: 120
50-Hz BIM 208 (Model 2500 only)
50-Hz BIM 220
50-Hz BIM 230
50-Hz BIM 240
*The UPS output voltage must match input voltage.
3. If your Bypass Module is a hardwired unit, supply utility power.
You have 30 seconds after supplying power to press the
Output
Off button. Release the Output
the alarm beeps. All indicators flash simultaneously.
4. If your Bypass Module is a plug/receptacle unit, plug the input
power supply cord into the utility input connector on the
Bypass Module rear panel.
Press and hold the Output
other end of the power supply cord into a grounded,
three-wire, AC receptacle that has been wired in accordance
with NEC specifications or national wiring rules (see Figure 12
for an example). Release the Output
alarm beeps. All indicators flash simultaneously.
Avaya Model 3000 UPS Operator's Manual
UPS Voltage Selection*
208
Set to 220V for 110/220V BDM output
Set to 230V for 115/230V BDM output
Set to 208V or 240V for 120/240V BDM output
Set to 220V for 110V BDM output
Set to 230V for 115V BDM output
Set to 208V or 240V for 120V BDM output
208
220
230
240
Off button when
Off button while plugging the
Off button when the
167-405-119 Issue 6 Uncontrolled Copy