Avaya Model 3000 UPS Operator's Manual
The black and white REPO wires are at high-voltage potential (240V). Refer to your
S
local electrical code for proper installation of the high-voltage REPO wires.
To ensure the UPS stops supplying power to the load during any mode of
S
operation, the input power must be disconnected from the UPS when the
emergency power-off function is activated.
1. Place the conduit through the access hole on the junction box
(see Figure 11). Connect the exposed conduit wires to the
corresponding compression terminals (see the following table).
Tighten the compression terminals with a screwdriver.
2. Pivot the REPO receptacle guard out of the way, plug the REPO
plug/receptacle UPS connector into the REPO receptacle on the
UPS rear panel and twist the connector in place (see Figure 5
on page 32 or Figure 6 on page 33).
Access Hole
for Conduit
Power Cable Terminations
Wire Function
REPO
L1
L2
Ground
*Suggested wire size is #18-AWG (0.75 mm
The REPO function activates when L1 and L2 are shorted together.
N N N N O O O O T T T T E E E E
167-405-119 Issue 6 Uncontrolled Copy
S
C A U T I O N
Mounting Holes
Terminal Block
Figure 11. REPO Cord Junction Box
Terminal
Terminal Wire
Position
Size Rating*
TB1-4
12 - 22 AWG
TB1-5
2
2
(4 - 0 mm
(4 - 0 mm
)
)
TB1-6
2
) 75
C copper wire minimum.
°
Installation
Plug/Receptacle
UPS Connector
Three Foot Cord
Tightening Torque
Entrelec
Phoenix
Contact
3.5 - 5.3 lb in
5.6 - 6.8 lb in
39