Avaya 1 Series Site Preparation, Installation And Operator's Manual page 60

200-240 v
Table of Contents

Advertisement

UPS Operation
Use the following procedure to reinstall the UPS and transfer the critical
load from Maintenance Bypass (AC Line operation) to the UPS:
50
1. Reconnect the battery module to the battery connector on the
UPS rear panel.
2. Switch the circuit breaker on all battery modules to the ON (
position.
3. Steps 4 through 8 are for changing the output voltage. The
output voltage is factory-configured for 208V. If you do not
need to change the UPS output voltage, skip to Step 9. Use the
following table to select the correct output voltage according to
your Bypass Module.
Bypass Module Model Number
60-Hz BDM 208: 120/208
60-Hz BDM 208/240: 120/240
60-Hz BDM 208/240: 120
50-Hz BIM 208 (Model 2500 only)
50-Hz BIM 220
50-Hz BIM 230
50-Hz BIM 240
*The UPS output voltage must match input voltage.
4. Press and hold the Output
Y-cord of the Bypass Module into the power connectors on the
UPS as shown in Figure 20.
Release the Output
All indicators flash simultaneously.
Avaya Model 3000 UPS Operator's Manual
UPS Voltage Selection*
Set to 220V for 110/220V BDM output
Set to 230V for 115/230V BDM output
Set to 208V or 240V for 120/240V BDM output
Set to 220V for 110V BDM output
Set to 230V for 115V BDM output
Set to 208V or 240V for 120V BDM output
Off button while plugging the
Off button when the alarm beeps.
167-405-119 Issue 6 Uncontrolled Copy
S
)
|
208
208
220
230
240