Troubleshooting
Condition
Communications do not
function properly.
f
i
l
No output load voltage.
p
g
OVERLOAD
I1
I2
I3
OUTPUT ON
OVERLOAD
I1
I2
I3
OUTPUT ON
OVERLOAD
I1
I2
I3
OUTPUT ON
OVERLOAD
I1
I2
I3
OUTPUT ON
OVERLOAD
I1
I2
I2
I3
OUTPUT ON
68
Possible Cause
Incorrect communications cabling.
Incorrect baud rate.
Incorrect communication mode.
Load plug(s) not fully seated.
Load circuit protectors tripped.
Power requirements exceed UPS
capacity. If overload is greater than
105%, the alarm beeps every second
and the UPS may switch to Bypass
mode.
The UPS switched to Bypass mode
because the overload increased
(above 105%). The alarm beeps.
The utility line voltage and frequency
are out of specification.
UPS internal temperature is too high.
The alarm beeps and the UPS
switches to Bypass mode for
approximately 10 minutes, allowing
the UPS to cool down.
Weak battery while in Normal mode.
The alarm beeps.
Battery breaker is open (O).
Battery module is not properly
connected to the UPS.
Avaya Model 3000 UPS Operator's Manual
Action
Verify cable integrity (see page 59).
Select a new baud rate (see page 59).
Select a new communication mode (see
Chapter 5).
Verify load plug(s) are fully seated.
Reset load protectors.
Your UPS continues to operate.
Reduce load.
Reduce load.
If the Overload indicator remains lit, reset
the UPS by pressing the Output
until the alarm beeps.
You may need to obtain a larger capacity
UPS.
The inverter remains online, deriving power
from the utility until it is no longer
acceptable.
Check the unit configuration.
Refer to the product specifications (see
page 63).
Shut down the UPS. Clear vents. Remove
any heat sources. Wait approximately
5 minutes and retry.
Contact your service representative if
condition persists.
Allow the battery to charge for 24 hours,
then retest. Have batteries replaced if
condition persists.
Make sure the battery module breaker is in
the ON (
) position.
|
Verify that the battery cords are connected.
167-405-119 Issue 6 Uncontrolled Copy