Installation
36
For Bypass systems with hardwired outputs, overcurrent protection and suitably rated
disconnect switches for the output AC circuit(s) are to be provided by either the
protected equipment or the customer's distribution panel.
21. Connect standard half-inch conduit through the terminal access
box (see Figure 7) and hardwire to the terminal block. See
Figure 8 and Figure 9 for the 60-Hz hardwired BDM wiring or
Figure 10 for the 50-Hz hardwired BIM wiring.
NOTE 208 Vac single phase is available between L2 (5) and L1 (4). However, the
voltage available between N (6) and L1 (4) is only 88 Vac
unless special requirements exist for 208 Vac, 120/240 Vac should be wired to the
customer provided distribution panel.
Figure 8. 60-Hz Hardwired Output Connections
Avaya Model 3000 UPS Operator's Manual
C A U T I O N
See note
+120V
Ground
88V
Neutral
-120V
NOT
167-405-119 Issue 6 Uncontrolled Copy
S
To customer
provided
240V
distribution
panel.
120 Vac. Therefore,