Access Cover
Screw
Input Breaker
1/2
Input
I
Conduit Access
Access Cover
Screw
Figure 7. UPS with Hardwired Bypass Module Rear Panel
Avaya Model 3000 UPS Operator's Manual
16. The equipment to be protected by the UPS should be powered
off. Plug the equipment into the power output receptacles on
the Bypass Module rear panel.
DO NOT protect laser printers with the UPS because of the
exceptionally high power requirements of the heating elements.
17. If you are using a Remote Emergency Power-Off (REPO)
switch, follow the instructions in "REPO Installation" on
page 38.
18. Start the UPS according to the "UPS with Bypass Module
Startup" procedure on page 40.
19. Refer to your national and local electrical codes for acceptable
external wiring practices.
Only qualified service personnel (such as a licensed electrician) should perform the
hardwired installation.
20. Remove the three screws on the terminal block access cover
with a Phillips screwdriver and remove the cover (see
Figure 7).
167-405-119 Issue 6 Uncontrolled Copy
S
W A R N I N G
BDM Input Voltage Selector Switch
Installation
Access Cover
Screw
Bypass Switch
Terminal Block
Access Cover
1/2
Output
I
Conduit Access
35