Avaya Model 3000 UPS Operator's Manual
5. Press and hold the Output On button until the alarm beeps
again.
Two indicators, corresponding with the current setting, remain
flashing. The output voltage is factory-configured for 230V.
OVERLOAD
I1
I2
I3
OUTPUT ON
6. Press the Output
voltage options, top to bottom. Each time you press the button,
the UPS beeps and the next two indicators flash.
NOTE If you do not save a selection within two minutes, the setup automatically
aborts and switches back to the original configuration.
7. Press and hold the Output On button until the alarm beeps to
select and save the output voltage. Failure to release the button
immediately after the beep will cause the UPS to abort the
setup.
8. Continue to Step 10.
9. Plug the Y-cord of the Bypass Module into the power
connectors on the UPS as shown in Figure 20.
10. Press and hold the Output On button until you hear the UPS
beep (approximately one second).
µ
The
i ndicator remains lit and the Output On indicator
turns on.
11. Turn the Bypass switch on the Bypass Module to the NORMAL
position.
The front panel displays the percentage of full load being
applied to the UPS. The UPS is now in Normal mode with the
load online.
167-405-119 Issue 6 Uncontrolled Copy
S
240V
230V
Figure 21. Output Voltage Indicators
Off button to scroll through the output
UPS Operation
220V
208V
51