5 Parameters
5.6 Operational data indicator
PNU
ID
P00-13
P00-14
P00-15
P00-16
P00-17
P00-18
15
16
P00-19
P00-20
12
13
14
104
Access
Value
right
ro/rw
ro
HH:MM:SS
ro
4 - 32 kHz
ro
0 - 1000 V
ro
-20 - 120 °C
ro
(0 - 2) x rated
operational
current
ro
ro
ro
Example: Status displays
The status displays of the digital inputs and outputs are equivalent. They can
be used to check whether an output control signal (e.g. from an external
controller) is activating the variable frequency drive's inputs (DI1 - DI4). This
provides you with an easy way to check the wiring (wire breakage).
The following table shows a few examples.
Display value: 1 = Activated = High; 0 = Not activated = Low
PNU
ID
P00-04
11
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
Description
The variable frequency drive's operating time since the last lockup
The variable frequency drive's operating time clock was stopped with the lockup.
→ Reset the value on next enable signal.
Pulse frequency
The variable frequency drive's actual effective output pulse frequency. If the variable
frequency drive gets too hot, this value can be lower than the frequency selected in P-17.
The variable frequency drive will automatically reduce the pulse frequency in order to
prevent a trip due to excess temperature and keep the system going.
DC bus voltage log (256 ms)
The eight most recent values before the trip
Updated every 250 ms.
Heat sink temperature memory
The last eight values before the trip. Updated every 500 ms.
Motor current memory
The last eight values before the trip. Updated every 250 ms.
Control section software version
Power section software version
Serial number of variable frequency drive
Unique variable frequency drive serial number (example: 540102 / 32 / 005)
Variable frequency drive part no.
Rated power of variable frequency drive
Firmware Version
Display value
Description
0000
No digital input (DI1, DI2, DI3, DI4) is actuated
1000
Control signal terminal 2 actuated (DI1)
0100
Control signal terminal 3 actuated (DI2)
0010
Control signal terminal 4 actuated (DI3)
0001
Control signal terminal 6 actuated (DI4)
0101
Control signal terminals 3 and 6 actuated (DI2 + DI4)