4 Operation
4.5 Commissioning with keypad
4.5 Commissioning with keypad
Sequence
Commands
1
2
90
The frequency reference value settings configured via the keypad have the
same effect as the function of an electronic motor potentiometer. The value
set with the ▲ and ▼ buttons will be retained even after the supply voltage is
switched off.
For control via the keypad, control signal terminal 1 must be
connected to control signal terminal 2 in order to get an enable.
The following table shows a good example of specifying the frequency
reference value via the operating unit.
Note: Your unit may behave differently from the description below
depending on the setting configured for P-15.
View
DC1 variable frequency drive 12/13 MN04020003Z-EN www.eaton.com
Description
Set parameter P-12 to 1 or 2 in order to hand over control
to the keypad.
1: Operating unit (keypad FWD): one operating direction
2: Operating unit (keypad FWD/REV): both operating
directions
Connect control signal terminal 1 to control signal
terminal 2 in order to get a start enable.
Press the Stop pushbutton in order to get to the setpoint
input display automatically.
Use the ▲ and ▼ arrow keys to change the setpoint
value.