Installation
DC Power Installation Procedure
The positive and negative wires can be installed pointing either to the right or to the left as long as
the terminal cover is used. The figure below shows them pointed to the right. Panduit LCD4-14A-L
connectors may be used for the supply and return wires, and Panduit LCD4-14AF-L or equivalent
connectors may be used for the 90-degree ground lug wire. Both connections have double lugs with
.25 inch holes measuring .625 inches from center to center.
Figure 29: Connecting DC Power to the Chassis (shows DC PDU only, Chassis is Omitted)
Cisco UCS 5108 Server Chassis Installation Guide
48