Installation
Note
Step 6
Connect the server chassis to the fabric interconnect as described in
Connectivity, on page
Both grids in a power redundant system should have the same number of power supplies. If your
system is configured for grid redundancy, slots 1 and 2 are assigned to grid 1 and slots 3 and 4 are
assigned to grid 2. If only two power supplies (PS) are in a redundant- mode chassis, they should
be in slots 1 and 3. Slot and cord connection numbering is shown below.
Figure 26: Power Supply Bay and Connector Numbering
50.
Inserting the Chassis into the Rack
Proper FEX and Fabric Interconnect Port
Cisco UCS 5108 Server Chassis Installation Guide
43