6.5.6 Setting 2 V ... 10 V (NE 43)
V
5.125
5.0
1.0
0.95
0
-1.25
At this setting, the start value of the measurement range is converted to 2 V and the end value to 10 V.
Intermediate values are converted proportionately.
If the value falls below the start value, the output voltage decreases linearly to a minimum of 1.9 V
(-1.25 % of the measurement range). Further decreases cannot be evaluated (output 1.9 V). If the
value exceeds the end value, the output voltage increases linearly to a maximum of 10.25 V
(approx. 103 % of the measurement range). Further increases cannot be evaluated (output 10.25 V).
6.5.7 Setting 1 V ... 5 V limited
V
5.0
1.0
0
At this setting, the start value of the measurement range is converted to 2 V and the end value to 10 V.
Intermediate values are converted proportionately.
Values below the start value cannot be evaluated (output 2 V). Values above the end value cannot be
evaluated either (output 10 V).
0
Start value
0
Start value
≈ 103
100
% Meas.
End value
range
100
% Meas.
End value
range