Frequency Converter HiD2891
If the value should be displayed in l/min, l/h or m³/h, m/s or km/h, the number of input pulses per
liter, per m³, km or m must be entered (see Divider parameter). Then the units are converted as
follows:
Hz x 60
l/min =
Pulses per liter
Hz x 3600
l/h =
Pulses per liter
Hz x 3600
m³/h =
Pulses per m³
Hz x 1000
m/s =
Pulses per km
Hz x 3600
km/h =
Pulses per km
Smoothing:
If values deviate sharply, smoothing can affect how quickly an output responds to a change in an
input value:
− 0 s = no smoothing
− 255 s = maximum smoothing
Divider:
The Pulse/unit menu item only appears if you have selected a unit other than Hz for the value
display (see Unit parameter).
Enter the number of pulses per revolution, per liter, per m³ or per km, depending on the selected
unit. The conversion is performed as described in the Unit parameter.
32
(measuring range restricted to 0.001 Hz ... 550 Hz
(measuring range restricted to 0.001 Hz ... 550 Hz
(measuring range restricted to 0.001 Hz ... 2 kHz)
(measuring range rstricted to 0.001 Hz ... 550 Hz)