Ametek Surgex UPS-17202-53R User Manual page 51

Online battery backup, 2000/3000 va
Hide thumbs Also See for Surgex UPS-17202-53R:
Table of Contents

Advertisement

_________________________________________________________________
Specification
UPS Model
Voltage (Nominal)
Battery Type
Battery Quantity
Recharge Time
Length
Height
Depth
Unit Weight
Shipping Weight
Safety Agencies
UPS-17302-60R Typical run times with external battery cabinets
Percent
Watts
Capacit
y
Runtimes are expressed in minutes
Typical runtimes based on fully charged, new batteries, operating under typical load conditions
Times estimated assuming a switch mode power supply
Runtimes are affected by batter age, ambient temperature, site specific usage
patterns and load conditions
0
0
1
240
0
2
480
0
3
720
0
4
960
0
5
1200
0
6
1440
0
7
1680
0
8
1920
0
9
2160
0
10
2400
0
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / surgex.com
Number of Battery Cabinets
Internal
INT+1 EXT
351
> 16 hrs.
56
247
26
117
16
72
11
51
8.8
38
7.0
31
5.7
25
4.8
21
4.1
18
3.6
16
UPS-BPX-3000
UPS-17302-60R
72.0 VDC
12V Flame Retardant Sealed Lead-Acid
6 x 2 Strings
24 Hours (Single Battery, 1A Charger)
17.25 in / 438 mm
3.39 in / 86 mm
24.92 in / 633 mm
91.5 lbs. / 41.6 kg
105.0 lbs. / 47.4 kg
UL1778 cUL to CSA22.2 No. 107.1
INT+2 EXT
INT+3 EXT
> 16 hrs.
491
232
144
101
77
61
50
42
36
31
User Manual
INT+4 EXT
> 16 hrs.
> 16 hrs.
772
> 16 hrs.
365
512
226
318
159
223
120
169
96
134
78
110
66
93
57
80
49
69
46

Advertisement

Table of Contents
loading

This manual is also suitable for:

Surgex ups-17302-60r

Table of Contents