Ametek UPS-I000-OL User Manual

Ametek UPS-I000-OL User Manual

Online battery backup
Table of Contents

Advertisement

Quick Links

Online Battery Backup
UPS-1000-OL - 1000 VA UPS
UPS-2000-OL - 2000 VA UPS
UPS-3000-OL - 3000 VA UPS
User Manual
© 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com / UM-UPS-Standalone-Rev-C

Advertisement

Table of Contents
loading

Summary of Contents for Ametek UPS-I000-OL

  • Page 1 Online Battery Backup UPS-1000-OL - 1000 VA UPS UPS-2000-OL - 2000 VA UPS UPS-3000-OL - 3000 VA UPS User Manual © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com / UM-UPS-Standalone-Rev-C...
  • Page 2: Table Of Contents

    Table of Contents Introduction 1.1 Technical Support 1.2 FCC Compliance 1.3 Safety Compliance 1.4 About This Manual 1.5 Safety 1.5.1 Safety Intended Use 1.5.2 General Warnings 1.5.3 Safety Notices 1.5.4 Battery Safety 1.5.5 Repacking of Unit Overview 2.1 UPS Devices and Batteries 2.2 Packing List 2.3 Storage 2.4 Recharging the UPS During Storage...
  • Page 3 5. UPS Operation 5.1 UPS input connection 5.1.1 LCD Display in Bypass Mode 5.1.2 LCD Display in Standby Mode 5.2 Turn on the UPS (Put the UPS in OnLine Mode) 5.2.1 LCD Display in OnLine Mode 5.3 Connect Devices to the UPS 5.4 The UPS in Battery Mode 5.4.1 LCD Display in Battery Mode 5.5 Turn off the UPS...
  • Page 4: Introduction

    CAUTION: Indicates instructions, which if not observed, present risk of electric shock, may endanger your life, your health, reliability of your UPS or the security of your data. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 5: Safety

    CAUTION: To reduce the risk of fire, connect models UPS-1000-OL and UPS-2000-OL only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 6 Emergency power off (EPO) is located on the rear of the unit (see Section 2.7 “Rear Panel View”). · When this connection is open, the logic circuit will immediately shut down the UPS output. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 7: Battery Safety

    Place the equipment in bags made of material sufficiently porous to allow it to breathe (e.g. 100μm polyethylene). Do not remove air from the packaging. When packing the unit for movement by common carrier, place in original or equivalent packaging container. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 8: Overview

    NOTE: When storing equipment, every 8°C above 25°C reduces the shelf life of the battery by 50%. More frequent battery charging is required to maintain the batteries in storage at these greater temperatures. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 9: Recharging The Ups During Storage

    It is necessary to leave a minimum space of at least two inches (50 mm) in front and rear of the UPS to allow a flow of air. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 10: Rear Panel View

    2.8 Rear Panel View 2.8.1 Models: UPS-1000-OL 2.8.2 Model: UPS-2000-OL 2.8.3 Model: UPS-3000-OL © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 11: Lcd Display

    2.9 LCD Display 2.9.1 Rack Display 2.9.2 Tower Display © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 12: Lcd: Display And Functional Description

    Indicates that the battery charger is working. Battery information Indicates the battery level by 0-25%, 26-50%, 51-75%, and 76 - 100%. Indicates low battery. Indicates that there is something wrong with the battery. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 13: Installation

    NOTE: When installing the UPS or external battery pack with feet, please keep both feet a distance of 2.75in (70mm) from the edge of the unit. See figure below: © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 14: Rack Installation

    Step 1: Use four M6 screws to mount the right and left rail sliders to the two front posts of the four-post rack. Refer to the figure directly below: © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 15 Add mounting ears to both sides of the unit and refer to figure directly below: Step 5. Install UPS and external battery pack. Refer to figure directly below: © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 16: Electrical Preparations

    CAUTION: Before connecting a battery pack to the UPS, the circuit breaker of the battery pack must be switched to “OFF”. After electrical connection with the UPS is established, the breaker must be switched to “ON”. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 17 Connect the other end of the battery cable to the UPS. For multiple extended battery packs, connect the supplied battery cables as shown in the figure below. Set the circuit breaker to the “ON” position. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 18: Setting Up Ups Parameters

    UPS status window on the LCD display. LCD Display in Bypass Mode Rack Display NOTE: The LCD will display the actual input voltage in the input/output and battery window. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 19: Output Voltage Setting (Item 01)

    DIS: converter mode is disabled. The output frequency is equal to the input frequency and the output voltage will be equal to the value chosen in section 4.2.1. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 20: Output Frequency Setting (Item 03)

    DIS: Programmable outlets are disabled. When the UPS goes to battery mode the programmable outlets will supply power to the connected load until the battery becomes depleted. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 21: Programmable Outlets Setting (Item 08)

    The following number of external battery packs can be chosen: 0: No External Battery Pack. 1: One External Battery Pack. 2: Two External Battery Packs. 3: Three External Battery Packs. 4: Four External Battery Packs. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 22: Ups Operation

    See Section 5.1.2 “LCD Display in Standby Mode”. 5.1.1 LCD Display in Bypass Mode Rack Display Tower Display 5.1.2 LCD Display in Standby Mode Rack Display Tower Display © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 23: Turn On The Ups (Put The Ups In Online Mode)

    5) After repetitive overloads, the UPS will be locked in bypass mode. Remove excess loads from the UPS output. Then restart the UPS. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 24: The Ups In Battery Mode

    If instead the bypass is disabled, the UPS will enter standby mode. In this mode the UPS will not supply power to the load. The UPS will also charge the batteries. See Section 5.1.2 “LCD Display in Standby Mode”. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 25: Interfaces

    · SNMP adapter (Manage UPS ) for Connecting the Device to a Network · Isolated Contacts Card Refer to the installation guide supplied with the optional interface card. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 26: Emergency Power Off (Epo)

    After charging, note the date recharging was performed on the UPS packaging. 8.3 Battery Testing 1. The UPS does not require maintenance by the user; however, the battery should be checked periodically. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 27: Replacing Batteries

    · Remove watches, rings or other metal objects. · Use tools with insulated handles. Do not lay tools or metal parts on top of batteries. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 28 Cut the tie holding the two halves of the battery pack connector. Disconnect the battery connectors. Refer to the figures directly below: 4. Pull out the battery pack. Refer to the figure directly below: © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 29 9. Carefully pack used battery pack and send to authorized recycle center. Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 30: Troubleshooting

    UPS is locked UPS output. Then shut down the in the bypass mode. Con- UPS and restart it. nected devices are fed directly by the mains. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 31 UPS beeping continuously and the output of circuited. before the UPS is repaired then the UPS is cut off. the DC/DC mosfet will be dam- aged. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 32: Audible Alarm

    Battery is Not Connected Overcharge Site Fault Over Temperature Charger Failure Battery Fault Frequency is Unstable in Bypass Mode Input Voltage is Out of Bypass Range EEPROM Error © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 33: Warning Indicators

    Beeps Once Every Second Battery Fault Beeps Once Every Second Bypass Out Range Beeps Once Every Second Bypass Frequency Unstable Beeps Once Every Second EEPROM Error Beeps Once Every Second © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 34: Ups Fault

    Inverter Output Short Bus Under Battery Voltage Too High Bus Unbalance Battery Voltage Too Low Bus Short Circuited Over Temperature Inverter Soft Start Fail Overload High Inverter Voltage © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 35: Appendix A: Specifications

    Battery Voltage (Float / Nominal) 27.4/24.0 VDC Charger Current 1.0 A Backup Time (Full Load) >3.5 Minutes Communications Interface USB / RS-232 Shipping Weight 37.0 lbs. / 16.8 kg. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 36 IEC61000-2-2, Low Frequency Signal • • (3) NEMA 5-15R Programmable RoHS • USB & RS-232 Communication • SNMP Adapter (Optional) • Internal Relay Contact Card (Optional) • Circuit Breaker © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 37 Battery Voltage (Float / Nominal) 54.7/48.0 VDC Charger Current 1.0 A Backup Time (Full Load) >3.6 Minutes Communications Interface USB / RS-232 Shipping Weight 58.0 lbs. / 26.4 kg. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 38 (2) NEMA 5-20R Programmable • IEC61000-2-2, Low Frequency Signal • USB & RS-232 Communication • • RoHS SNMP Adapter (Optional) • Internal Relay Contact Card (Optional) • Circuit Breaker © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 39 Battery Voltage (Float / Nominal) 82.1/72.0 VDC Charger Current 1.0 A Backup Time (Full Load) >3.6 Minutes Communications Interface USB / RS-232 Shipping Weight 81.0 lbs. / 36.8 kg. © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 40 IEC61000-4-8, Power Frequency Magnetic Field • • USB & RS-232 Communication IEC61000-2-2, Low Frequency Signal • SNMP Adapter (Optional) • RoHS • Internal Relay Contact Card (Optional) • (2) Circuit Breakers © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 41: Extension Battery Packs For Use With Surgex Ups's

    Depth 16.26 in / 413 mm Unit Weight 38.0 lbs. / 17.3 kg. Shipping Weight 47.0 lbs. / 21.4 kg. UL1778 Safety Agencies cUL to CSA22.2 No. 107.1 © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 42 Runtimes are affected by battery age, ambient temperature, site specific usage patterns and load conditions > 16 hrs > 16 hrs > 16 hrs > 16 hrs > 16 hrs 1120 1280 1440 1600 © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 43 Runtimes are affected by battery age, ambient temperature, site specific usage patterns and load conditions > 16 hrs > 16 hrs > 16 hrs > 16 hrs > 16 hrs 1200 1440 1680 1920 2160 2400 © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...
  • Page 44 © 2017 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com...