Ametek Surgex UPS-17202-53R User Manual page 39

Online battery backup, 2000/3000 va
Hide thumbs Also See for Surgex UPS-17202-53R:
Table of Contents

Advertisement

_________________________________________________________________
Do not dispose of batteries in a fire. The batteries may
explode.
Do not open or damage the battery cases. Released electrolyte is
harmful to the skin and eyes and may be toxic.
A battery can present a risk of electrical shock and high short-cir-
cuit current. The following precautions should be observed when
working on batteries:
Remove watches, rings or other metal objects.
Use tools with insulated handles. Do not lay tools or metal
parts on top of batteries.
This UPS is equipped with internal batteries. The user can replace the
batteries without shutting down the UPS or connected loads (hot-swap-
pable battery design). Replacement is a safe procedure - isolated from
electrical hazards.
Consider all warnings, cautions, and notes before replacing batteries.
The load attached to the UPS will not be protected against loss of
input power during this procedure.
The battery pack is heavy. Use two hands when removing pack
from unit.
The battery packs for the UPS-17302-60R are not user replace-
able. Contact technical support to arrange for maintenance and
battery replacement.
To replace internal batteries:
1. Place the UPS in bypass mode.
2. Place fingers on the left-hand side of the front cover and pull
forward until the left side of the front cover "snaps" out of position.
Remove the left side of the front cover and place it in a safe place.
Refer to the following figure:
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / surgex.com