Storage Temperature
-13°F to 104°F (-25°C to +40°C)
104°F to 113°F (40°C to +45°C)

2.5 Environmental Conditions

The UPS must be installed on a level and even surface. Install in an area
protected from extremes of temperature, water, humidity and the pres-
ence of conductive powder or dust. Do not stack units and do not place
any objects on top of a unit.
The functional temperature range of the UPS is 32°F to 104°F (0°C to
+40°C).
The ideal ambient temperature range is 60°F to 77°F (15°C to 25°C).
Expected battery runtimes and battery life is based on operational tem-
peratures between 68°F and 77°F (20°C and 25°C). Operation of the
equipment above 77°F (25°C) reduces the service life of the batteries
dramatically.

2.6 Floor Loading

Taking into consideration the weight of the UPS, extended battery cab-
inets, and any other equipment that may be mounted in an associated
rack. Confirm that the floor chosen location is capable of
supporting the weight of the combined units.

2.7 Ventilation

It is necessary to leave a minimum space of at least two inches (50 mm)
in front and rear of the UPS to allow a flow of air.
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / surgex.com
Recharge Frequency
Every 3 Months
Every 2 Months
User Manual
Charging Duration
1-2 Hours
1-2 Hours
9