_________________________________________________________________
4.2.7 LCD Display Direction Setting (Item 09)
Interface
4.2.8 Acceptable Input Voltage Range Setting (Item 10)
Interface
4.2.9 Number of External Battery Cabinets (Item 11)
Interface
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / surgex.com
Setting
RAC: the LCD display is horizontal.
TOE: the LCD display is vertical.
Setting
Display alternates between low and high voltage of the
range. The following acceptable input voltage range may
be chosen:
200 - 240 Volt Models
170/240: 170-240 V Input Range
160/260: 160-260 V Input Range
180/300: 180-300 V Input Range
Setting
The following number of external battery cabinets can be
chosen:
0: No External Battery Cabinet.
1: One External Battery Cabinet.
2: Two External Battery Cabinets.
3: Three External Battery Cabinets.
4: Four External Battery Cabinets.
User Manual
100 - 120 Volt Models
85/135 : 85-135 V Input Range
80/130: 80-130 V Input Range
55/150: 55-150 V Input Range
25