Page 3
IMPORTANT NOTICE ON BATTERY WARRANTY The warranty policy stated in Section 8 is not valid for applications in which the UPM is regularly and intentionally disconnected from AC mains power. The two year battery warranty applies only to products that are properly installed and consistently connected to AC mains power, except during utility outages.
Page 4
Danger- The danger symbol is used to indicate imminently hazardous situations, locations, and conditions which, if not avoided, WILL result in death, serious injury, and/or severe property damage. DANGER Caution- The caution symbol is used to in- dicate potentially hazardous situations and conditions which, if not avoided, may result in CAUTION injury.
Page 5
Alternating Current Refer to instruction manual/booklet. Two person lift. A01-00104 Rev A...
If, after reviewing this manual, you have any questions at all, please feel free to contact our technical support team by phone (1-800-369-7179) or email us at service.powervar@ametek.com. We are a global provider of power management solutions, headquartered in Waukegan, Illinois, with international sales and distribution offices in Swin- don, United Kingdom, Toronto, Canada, Mexico City, Mexico and Germany.
Page 7
General The Security II UPM (hereafter refered to as “UPM”) systems are the most advanced, line interactive, true sinewave UPS products available for your application. Each model is designed to provide total protection for your system from a complete range of power quality problems. UPM systems will protect your installation from normal mode voltage impulses, electrical noise, sags, surges, brownouts, and blackouts.
2.0 SAFETY INSTRUCTIONS IMPORTANT - SAVE THESE INSTRUCTIONS THIS MANUAL CONTAINS IMPORTANT SAFETY INSTRUCTIONS. KEEP THIS MANUAL HANDY FOR REFERENCE. CAUTION A battery can present a risk of electrical shock. Short-circuit currents can be extremely high and can create severe burns as well as the risk of fire or explosion from vented gases.
Page 9
STATEMENT OF INTENDED USE The medical UPMs are intended to protect medical, non-medical computer equipment and medical devices that need battery backup, surge protection, voltage regulation and line noise filtering in and around patient care areas. Safe and continuous operation of the UPM depends partially on the care tak- en by users.
Page 10
• The total leakage current of the UPM and consumer connected equip- ment should not exceed 3.5 mA for non-medical units. • Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment, ANSI/ NFPA 75.
Page 11
FCC ISSUES Attention This UPM has been tested and found to comply with the limits for a Class A digital devices (Class B compliance optional), pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in both residential and commercial environments.
3.0 INSTALLATION Security II Rackmount Quick Start Guide This unit is shipped with the internal batteries disconnected. Before starting the UPM, please follow these battery connection instructions. Remove UPM from the box Some units may require 2 people to lift. Attached included outlet cord and plug UPM into wall.
Page 13
Security II Rackmount Quick Start Guide Connect battery connector. Battery connectors may be partially hidden on the side of the battery. *The 2.2 & 3KVA units connect 2 batteries Put they metal battery cover and the front cover back on and remove the yellow warning label.
Page 14
UNPACKING THE UPM CAUTION • Unpacking the unit in a low-temperature environment may cause condensation to occur in and on the unit. Do not install the unit until the inside and outside of the unit are absolutely dry {hazard of electric shock}.
Page 15
Rackmount Installation Guide Assemble the side rails and secure each with (2) screws. Each unit and each battery DO NOT TIGHTEN. cabinet must be mounted to their own rail kits that Attach front of the rails to are included. front of rack with (1) fastener for each side in the upper mounting hole.
Page 16
Rackmount Installation Guide INSPECTING THE UPM If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage: 1. File with the carrier within 15 days of receipt of the equipment; 2.
4.0 OPERATION NOTE: In order to operate the UPM, you must first plug the battery enable plug(s) into the battery enable socket(s) behind the front panel of the UPM. On/Off Button The On/Off button is a dual function control: • When the UPM is off and AC power is present to the UPM input, pressing the On/Off button for more than 2 seconds will turn the UPM output on.
Page 18
Load Monitor The Load Monitor is a six-segment LED display that shows the current load percentage. The first 5 LED’s each indicate approximately 20% load, with the 6th red LED showing the UPM is overloaded. Battery Charge Monitor The Battery Charge Monitor is a five-segment LED display that shows the charge capacity of the internal battery from zero to 100%.
Page 19
Display Functionality The location should provide adequate airflow around the UPM. Pro- vide a minimum 3” clearance on all sides for proper ventilation. Applying Power to the UPM Connect the power cord to a verified grounded 3 wire receptacle. Verify that the Site Wiring Fault “SF”...
UPM Load and Battery Indicators Example: UPM display showing normal operation (Fully charged batteries with 60% load shown) UPM display showing in battery backup operation (Batteries 80% charged with 60% load shown) UPM display showing an overload condition (Batteries 100% charged and greater than 100% load shown) UPM display showing over-temperature condition (Batteries 80% charged with 80% load shown)
Page 21
Reference the below UPM fault code chart to identify the status of the UPM. UPM Status Code Definition Inverter fault Back-Feed fault Unit is off due to a high line Unit is off due to a low line Unit is off due to a low battery Fan fault Site wiring fault NOTE:...
5.0 MAINTENANCE Storage The UPM may be stored for extended periods in an environment that does not subject the UPM to extremes of temperature or humidity. When storing for extended periods, the battery should be charged every six months. If the storage location is characterized by above normal temperature, the battery should be recharged every two months.
Page 23
Please familiarize yourself with the following precautions before proceeding with battery replacement. WARNING Servicing of batteries should always be performed or supervised by some- one who has read and understood the following precautions and who under- stands the hazards associated with storage batteries. This procedure should not be performed by someone who is unauthorized or who is incapable of following these precautions.
Page 24
User Replaceable Battery (Non-medical units only) Eventually every UPM requires a new battery. We expect the battery in your UPM to last a minimum of two years – perhaps longer if power outages are short and infrequent. The UPM makes battery replacement by the user fast and easy.
Page 25
Risk of Energy Hazard, 12V, maximum 23 Ampere-hour batteries. Before replacing batteries, remove conductive jewelry such as chains, wrist watch- es, and rings. High energy through conductive materials could cause severe burns. CAUTION Do not dispose of batteries in a fire. The batteries may explode. CAUTION Do not open or mutilate batteries.
NOTE: Both sets of batteries must be replaced at the same time to ensure proper operation and expected runtimes. See “Instruction for Returning a Depleted Battery Pack” for instructions on returning depleted battery(s) to AMETEK Powervar. * Battery connect on the front of the unit for the 4U units. A01-00074 Rev. C...
6.0 TROUBLESHOOTING The troubleshooting information provided in this section should help you discover the cause of most commonly encountered difficulties. Before follow- ing the troubleshooting steps provided, be certain that you have verified the following items: • The UPM should be plugged into a properly working outlet. •...
Replace with same type and rating of fuse fuse must be rated to IEC 60127-2 Model Fuse rating (slow-blow) ABCE702-11R / ABCE702-11RMED 250 VAC 6.3 A ABCE702-22R / ABCE702-22RMED 250 VAC 3.15 A ABCE1002-11R / ABCE1002-11RMED...
7.0 WARRANTY The Security II Series UPM is warranted to be free from defects in material and workmanship for sixty (60) months from date of shipment, on the chassis & electronic components and twenty four (24) months from date of shipment on the batteries.
8.0 SPECIFICATIONS Security II Rackmount UPM Specifications Security II Rackmount UPM Specifications North American 700 VA Models - Standard North American 700 VA Models - Standard MODEL NUMBER ABCE702-11R ABCE702-11R PART NUMBER 58070-08R 58070-01R Type Standard Standard Power Rating (VA/Watts)
Page 31
Security II Rackmount UPM Specifications North American 700 VA Models - Standard Front Panel Controls Safety Agency and EMC Compliance: • Power On/Off All Units are Listed by UL and Marked With the UL/cUL Marking • Test • Load Level LED Gauge Environmental •...
Page 32
Security II Rackmount UPM Specifications Security II Rackmount UPM Specifications North American 700 VA Models - Medical North American 700 VA Models - Medical MODEL NUMBER ABCE702-11RMED ABCE702-11RMED PART NUMBER 58070-28R 58070-21R Type Medical Grade Medical Grade Power Rating (VA/Watts) 700 / 630 700 / 630 Inverter Waveform...
Page 33
Security II Rackmount UPM Specifications North American 700 VA Models - Medical Security II Rackmount UPM Specifications North American 700 VA Models - Medical Front Panel Controls Environmental • Power On/Off • Temperature: 0 - +40℃(32 to 104℉) Operating • Test -20 to 60℃(-40 to 140℉) Shipment/ •...
Page 34
Security II Rackmount UPM Specifications International 700 VA Models - Standard Security II Rackmount UPM Specifications International 700 VA Models - Standard MODEL NUMBER ABCE702-22R PART NUMBER 59070-08R Type Standard Power Rating (VA/Watts) 700 / 630 Inverter Waveform Low Distortion Sine Wave Transfer Time 4 ms.
Page 35
Security II Rackmount UPM Specifications International 700 VA Models - Standard Security II Rackmount UPM Specifications International 700 VA Models - Standard Front Panel Controls Environmental • Power On/Off • Temperature: 0 - +40℃(32 to 104℉) Operating • Test -20 to 60℃(-40 to 140℉) Shipment/ •...
Page 36
Security II Rackmount UPM Specifications International 700 VA Models - Medical Security II Rackmount UPM Specifications International 700 VA Models - Medical MODEL NUMBER ABCE702-22RMED PART NUMBER 59070-28R Type Medical Grade Power Rating (VA/Watts) 700 / 630 Inverter Waveform Low Distortion Sine Wave Transfer Time 4 ms.
Page 37
Security II Rackmount UPM Specifications International 700 VA Models - Medical Security II Rackmount UPM Specifications International 700 VA Models - Medical Front Panel Controls Environmental • Power On/Off • Temperature: 0 - +40℃(32 to 104℉) Operating • Test -20 to 60℃(-40 to 140℉) Shipment/ •...
Page 38
Security II Rackmount UPM Specifications North American 1000 VA Models - Standard Security II Rackmount UPM Specifications North American 1000 VA Models - Standard MODEL NUMBER ABCE1002-11R ABCE1002-11R PART NUMBER 58100-08R 58100-01R Type Standard Standard Power Rating (VA/Watts) 1000 / 900 1000 / 900 Inverter Waveform Low Distortion Sine Wave...
Page 39
Security II Rackmount UPM Specifications North American 1000 VA Models - Standard Security II Rackmount UPM Specifications North American 1000 VA Models - Standard Front Panel Controls Environmental • Power On/Off • Temperature: 0 - +40℃(32 to 104℉) Operating • Test -20 to 60℃(-40 to 140℉) Shipment / Storage •...
Page 40
Security II Rackmount UPM Specifications Security II Rackmount UPM Specifications North American 1000 VA Models - Medical North American 1000 VA Models - Medical MODEL NUMBER ABCE1002-11RMED ABCE1002-11RMED PART NUMBER 58100-28R 58100-21R Type Medical Grade Medical Grade Power Rating (VA/Watts) 1000 / 900 1000 / 900 Inverter Waveform...
Page 41
Security II Rackmount UPM Specifications North American 1000 VA Models - Medical Security II Rackmount UPM Specifications North American 1000 VA Models - Medical Front Panel Controls Environmental • Power On/Off • Temperature: 0 - +40℃(32 to 104℉) Operating • Test -20 to 60℃(-40 to 140℉) Shipment / Storage •...
Page 42
Security II Rackmount UPM Specifications International 1000 VA Models - Standard Security II Rackmount UPM Specifications International 1000 VA Models - Standard MODEL NUMBER ABCE1002-22R PART NUMBER 59100-08R Type Standard Power Rating (VA/Watts) 1000 / 900 Inverter Waveform Low Distortion Sine Wave Transfer Time 4 ms.
Page 43
Security II Rackmount UPM Specifications International 1000 VA Models - Standard Security II Rackmount UPM Specifications International 1000 VA Models - Standard Front Panel Controls Environmental • Power On/Off • Temperature: 0 - +40℃(32 to 104℉) Operating • Test -20 to 60℃(-40 to 140℉) Shipment/ •...
Page 44
Security II Rackmount UPM Specifications International 1000 VA Models - Medical Security II Rackmount UPM Specifications International 1000 VA Models - Medical MODEL NUMBER ABCE1002-22RMED PART NUMBER 59100-28R Type Medical Grade Power Rating (VA/Watts) 1000 / 900 Inverter Waveform Low Distortion Sine Wave Transfer Time 4 ms.
Page 45
Security II Rackmount UPM Specifications International 1000 VA Models - Medical Security II Rackmount UPM Specifications International 1000 VA Models - Medical Front Panel Controls Environmental • Temperature: 0 - +40℃(32 to 104℉) Operating • Power On/Off -20 to 60℃(-40 to 140℉) Shipment/ •...
Page 46
Security II Rackmount UPM Specifications Security II Rackmount UPM Specifications North American 1440 VA Models - Standard North American 1440 VA Models - Standard MODEL NUMBER ABCE1442-11R ABCE1442-11R ABCE1442-11R PART NUMBER 58144-01R 58144-08R 58144-18R Type Standard Standard Standard Power Rating (VA/Watts) 1440 / 1296 1440 / 1296 1440 / 1296...
Page 47
Security II Rackmount UPM Specifications North American 1440 VA Models - Standard Security II Rackmount UPM Specifications North American 1440 VA Models - Standard Front Panel Controls Environmental • Power On/Off • Temperature: 0 - +40℃(32 to 104℉) Operating • Test -20 to 60℃(-40 to 140℉) Shipment/ •...
Page 48
Security II Rackmount UPM Specifications Security II Rackmount UPM Specifications North American 1440 VA Models - Medical North American 1440 VA Models - Standard MODEL NUMBER ABCE1442-11R ABCE1442-11R ABCE1442-11R PART NUMBER 58144-01R 58144-08R 58144-18R Type Standard Standard Standard Power Rating (VA/Watts) 1440 / 1296 1440 / 1296 1440 / 1296...
Page 49
Security II Rackmount UPM Specifications North American 1440 VA Models - Medical Security II Rackmount UPM Specifications North American 1440 VA Models - Standard Front Panel Controls Environmental • Power On/Off • Temperature: 0 - +40℃(32 to 104℉) Operating • Test -20 to 60℃(-40 to 140℉) Shipment/ •...
Page 50
Security II Rackmount UPM Specifications Security II Rackmount UPM Specifications International 1440 VA Models - Medical North American 1440 VA Models - Medical MODEL NUMBER ABCE1442-11RMED ABCE1442-11RMED PART NUMBER 58144-21R 58144-28R Type Medical Grade Medical Grade Power Rating (VA/Watts) 1440 / 1296 1440 / 1296 Inverter Waveform Low Distortion Sine Wave...
Page 51
Security II Rackmount UPM Specifications International 1440 VA Models - Medical Security II Rackmount UPM Specifications North American 1440 VA Models - Medical Front Panel Controls Environmental • Power On/Off • Temperature: 0 - +40℃(32 to 104℉) Operating • Test -20 to 60℃(-40 to 140℉) Shipment/ •...
Page 52
Security II Rackmount UPM Specifications International 1440 VA Models - Standard Security II Rackmount UPM Specifications International 1440 VA Models - Standard MODEL NUMBER ABCE1442-22R PART NUMBER 59144-08R Type Standard Power Rating (VA/Watts) 1440 / 1296 Inverter Waveform Low Distortion Sine Wave Transfer Time 4 ms.
Page 53
Security II Rackmount UPM Specifications International 1440 VA Models - Standard Security II Rackmount UPM Specifications International 1440 VA Models - Standard Front Panel Controls Environmental • Power On/Off • Temperature: 0 - +40℃(32 to 104℉) Operating • Test -20 to 60℃(-40 to 140℉) Shipment/ •...
Page 54
Security II Rackmount UPM Specifications Security II Rackmount UPM Specifications International 1440 VA Models - Medical International 1440 VA Models - Medical MODEL NUMBER ABCE1442-22RMED PART NUMBER 59144-28R Type Medical Grade Power Rating (VA/Watts) 1440 / 1296 Inverter Waveform Low Distortion Sine Wave Transfer Time 4 ms.
Page 55
Security II Rackmount UPM Specifications International 1440 VA Models - Medical Security II Rackmount UPM Specifications International 1440 VA Models - Medical Front Panel Controls Environmental • Power On/Off • Temperature: 0 - +40℃(32 to 104℉) Operating • Test -20 to 60℃(-40 to 140℉) Shipment/ •...
Page 56
Security II UPM Specifications Security II UPM Specifications North American Models ABCE2202-11R North American Models ABCE2202-11R ABCE2202-11R 58220-08R Type Standard Power Rating (VA/Watts) 2200 / 1980 Inverter Waveform Low Distortion Sine Wave Transfer Time 4 ms. Typical Frequency 50 / 60 Hz. BTU/Hr.
Page 57
Security II UPM Specifications North American Models ABCE2202-11R Front Panel Controls -20 to 60 C (-40 to 140 F) Shipment/ Storage Power On/Off Humidity: 5 to 90% Non-Condensing (Operating, Test Shipment/Storage) Load Level LED Gauge Altitude: 3,000m (10,000 ft) max.
Page 58
Security II UPM Specifications Security II UPM Specifications International Models ABCE2202-22R International Models ABCE2202-22R ABCE2202-22R 59220-08R Type Standard Power Rating (VA/Watts) 2200 / 1980 Inverter Waveform Low Distortion Sine Wave Transfer Time 4 ms. Typical Frequency 50 / 60 Hz. BTU/Hr.
Page 59
Security II UPM Specifications International Models ABCE2202-22R Front Panel Controls -20 to 60 C (-40 to 140 F) Shipment/ Storage Power On/Off Humidity: 5 to 90% Non-Condensing (Operating, Test Shipment/Storage) Load Level LED Gauge Altitude: 3,000m (10,000 ft) max.
Page 60
Security II UPM Specifications Security II UPM Specifications North American Models ABCE3002-21R North American Models ABCE3002-21R MODEL NUMBER ABCE3002-21R ABCE3002-21R PART NUMBER 59300-32R 59300-38R Type Standard Standard Power Rating (VA/Watts) 2760 / 2484 2760 / 2484 Inverter Waveform Low Distortion Sine Wave Low Distortion Sine Wave Transfer Time 4 ms.
Page 61
Security II UPM Specifications North American Models ABCE3002-21R Front Panel Controls Environmental Power On/Off Temperature: 0 - +40 C (32 to 104 F) Operating -20 to 60 C (-40 to 140 F) Shipment/ Test Storage Load Level LED Gauge ...
Page 62
Security II UPM Specifications Security II UPM Specifications International Models ABCE3002-22R International Models ABCE3002-22R ABCE3002-22R 59300-08R Type Standard Power Rating (VA/Watts) 2760 / 2484 Inverter Waveform Low Distortion Sine Wave Transfer Time 4 ms. Typical Frequency 50 / 60 Hz. BTU/Hr.
Page 63
Security II UPM Specifications International Models ABCE3002-22R Front Panel Controls -20 to 60 C (-40 to 140 F) Shipment/ Storage Power On/Off Humidity: 5 to 90% Non-Condensing (Operating, Test Shipment/Storage) Load Level LED Gauge Altitude: 3,000m (10,000 ft) max.
Page 64
Security II UPM Specifications Security II UPM Specifications North American Models ABCE2202-11R North American Models ABCE2202-11R MODEL NUMBER ABCE2202-11R ABCE2202-11R PART NUMBER 58220-10R 58220-38R Type Standard Standard Power Rating (VA/Watts) 1800/1620 1800/1620 Inverter Waveform Low Distortion Sine Wave Low Distortion Sine Wave Transfer Time 4 ms.
Page 65
Security II UPM Specifications North American Models ABCE2202-11R Front Panel Controls Humidity: 5 to 90% Non-Condensing (Operating, Power On/Off Shipment/Storage) Test Altitude: 3,000m (10,000 ft) max. Operating; 12,000m (40,000 ft) max. Shipment/Storage. Load Level LED Gauge ...
Page 66
USA Address: 1450 Lakeside Drive Waukegan, IL 60085 1-800-369-7179 (P) 847-596-7000 (F) 847-596-7100 Canada Address: 700 Finley Avenue, Unit 3 Ajax, Ontario L1S 3Z2 (P) 905-239-9284 Access additional product information and support on the web at http://www.powervar.com Europe/Asia Address: Unit 5, Birch-Kembrey Park A01-00104 Rev A –...