5.3 Loading data to the 'Station'

5.4 Initializing 'Station'

Building Technologies
Fire Safety
Data is loaded from Cerberus-Engineering-Tool to the 'Station' when the following
commands are performed.
'Initialize station'
'Download site'
If you use a number of network cards on the PC, observe the information in the
chapter 'IP settings for several network cards' in document A6V10210424. See
chapter 'Applicable documents'.
The table below shows which data is overwritten in the station 'Station'.
Command
'Initialize station'
1
'Download site'
Command is only performed for the 'Station' that is connected to the PC via LAN.
1
The configuration of all 'Stations' in the 'Site' can be overwritten as an option.
2
See also
Loading configuration from the PC to the 'Station' [
Initializing 'Station' [
Each 'Station' in a fire detection system with several networked 'Stations' must
have a unique address.
Once a 'Station' has been started for the first time or once the firmware on the
main CPU has been updated, a 'Station' has the address '1'. Networked
'Stations' must therefore all be initialized.
If two 'Sites' are merged to form one 'Site', the 'Stations' with the same
addresses in the added 'Site' must each be given a new address.
The 'Initialize station' procedure issues the 'Station' an address within the 'Site'
according to the configuration in Cerberus-Engineering-Tool.
A standalone 'Station' does not have to be initialized.
If you use a number of network cards on the PC, observe the information in the
chapter 'IP settings for several network cards' in document A6V10210424. See
chapter 'Applicable documents'.
Connectivity and communication with 'Station'
Loading data to the 'Station'
Overwrites the
Sets the address
BDV
of the 'Station'
Yes
Yes
Yes
No
21]
5
Overwrites the
configuration
Yes
Yes
2
23]
21
A6V10210416_f_en_--