General commissioning steps

Remove the elements

6.15
6.16
6.17
32
Building Technologies
Fire Safety
Remove the elements
If you have uninstalled an C-NET device for good, the corresponding elements,
e.g. the 'Zone' must be removed from the logical structure trees in Cerberus-
Engineering-Tool. You can search for elements using the 'Find' function.
You will find more information in document A6V10210424. See chapter 'Applicable
documents'.
See also
Applicable documents [

Switching on test mode

1. Select 'Topology' > 'Detection tree' in the main menu.
2. Select the element you want to switch to test mode: 'Area', 'Section' or 'Zone'.
3. Press the 'More Options' softkey and select 'Execute commands'.
4. Select a command from the following table.
The yellow 'DETECTORES EN PRUEBAS' LED lights up.
The element is in test mode.
Element
Area
Section
Zone

Switch on normal operation

There is a shortened procedure for switching individual 'Zones' to normal
operation. The procedure is described in the following section: ''Switching 'Zone'
to normal operation'
'Switching 'Area', 'Section' or 'Zone' to normal operation
1. Select 'Topology' > 'Detection tree' in the main menu.
2. Select the element you want to switch to normal operation: 'Area', 'Section' or
'Zone'.
3. Press the 'More Options' softkey and select 'Execute commands'.
4. Select a command from the following table.
The element is switched to normal operation.
The yellow 'DETECTORES EN PRUEBAS' LED goes out.
8]
Command
'Non-MCP zones det.test'
'MCP zones det.test'
'Non-MCP zones det.test'
'MCP zones det.test'
'Detector test'