Commissioning The Fire Brigade Periphery Module Fci2001-D1 - Siemens FS720 Commissioning, Maintenance, Troubleshooting

Fire detection system
Table of Contents

Advertisement

15 Commissioning the fire brigade periphery
Building Technologies
Fire Safety

Commissioning the fire brigade periphery module FCI2001-D1

module FCI2001-D1
The fire department periphery module FCI2001-D1 monitors the monitored inputs
and outputs for short-circuit and open line. The resistance values of the lines may
be read in and stored at the push of a button. If a deviation from the quiescent
value is detected, the control panel evaluates a short-circuit or an open line.
The following table shows the monitored inputs and outputs:
Terminal
Pin
X4
4, 5 and 1, 2
X5
7, 8
X6
5, 6
X5
X4
S101
View of the fire department periphery module
X4–X6
Connection terminals
S101
Button
Procedure
1. Check the connected lines for short-circuit and open line.
2. Connect the lines.
During the commissioning of the control panel, fault messages are
indicated, provided that there are any deviations from the basic settings.
3. Press the push-button S101.
The resistance values are read in.
Function
Remote transmission or transmission device (RT Alarm)
and release element ('FSE')
'Key depot' (tamper monitoring)
Local alarm
X6
15
57
A6V10210416_f_en_--
14.01.2013