14 Commissioning safety module (firewall)
Building Technologies
Fire Safety
FN2009-A1
This description focuses on correctly configuring and integrating the 'Security
module (firewall) FN2009-A1' in the fire detection installation. More information
about the product can be found on the data carrier in the scope of supply and at
the following address: http://support.automation.siemens.com (Manufacturer
designation: Scalance S612)
A configuration is available via the localization manager. We recommend using
the configuration and if necessary making system-specific adaptations.
Commissioning
1. Install the 'Security Configuration Tool' software. Link [
2. Select the type and enter the MAC address. Link [
3. Enter the network settings. Link [
-
Load configuration.
4. Create IP service definitions. Link [
5. Create firewall rules. Link [
-
Load configuration.
The 'Security module (firewall) FN2009-A1' is a class A equipment and may
cause radio interference in residential areas. If interference does occur, observe
the relevant information in document A6V10210390. See chapter 'Applicable
documents'.
The FN2009-A1 has no IP address in the factory setting. You must manually
assign the IP address.
NOTICE
FN2009-A1 is not in the factory setting and already has an IP address
It is not possible to upload a new configuration
Press the Reset button on the live FN2009-A1.

Commissioning safety module (firewall) FN2009-A1

Configure FN2008-A1 using Internet browser
51]
54]
55]
14
50]
50]
A6V10210416_f_en_--
14.01.2013
49